Menu 29 − Pump Closed-loop

Mode: RFC‑A

Menu 29 is where the Pump software control, status and configuration is located. The following diagrams give an overview of the functionality available.

 

 

 

 

 

 

 

 


Parameter29.001  Pump Software Version
Short descriptionThis is the version of the F600 derivative software
ModeRFC‑A
Minimum0Maximum99999999
Default Units 
Type32 Bit VolatileUpdate RateBackground
Display FormatVersionDecimal Places0
CodingRW, PR, ND, NC, PT

This parameter indicates the pump software version number in the format ww.xx.yy.zz e.g. 01.00.00.00.


Parameter29.002  Total Run Time
Short descriptionIndicates the total running time in hours
ModeRFC‑A
Minimum0Maximum65535
Default0Unitshours
Type16 Bit Power Down SaveUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, NC, PT, BU

This parameter indicates the total running time so far for this drive. This is the time while the motor is being commanded to run.


Parameter29.003  Operating Status
Short descriptionIndicates which operating state the drive is in
ModeRFC‑A
Minimum0Maximum38
Default0Units 
Type8 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, PR, TE, NC, PT, BU

ValueText
0Inhibit STO
1Off (Ready)
2Hand Run
3Waking
4Pipe Fill
5Auto Run
6Auto Run Leader
7Auto Run Assist
8Pre-sleep
9Sleeping
10Cleaning
11Level Stop
12Timer Stop
13Hand Timeout
14Over-cycle
15Fbck Loss Run
16Dry Well Run
17Dry Well Stop
18Auto Stop Assist
19Trip
20Under Voltage
21Hand Stop
22Auto Stop
23No Flow Stop
24Inhibit
25Ready
26Stop
27Scan
28Run
29Supply Loss
30Deceleration
31dc Injection
32Position
33Active
34Off
35Hand
36Auto
37Heat
38Phasing

This parameter indicates the operating status of the pump software. This forms an important diagnostic aid which tells the user what the system is doing at any moment and why e.g. if the pump has gone to sleep or stopped the operating status will indicate why. The following table shows all of the status values:

Status Value Description
Inhibit STO 0 The drive is inhibited i.e. the STO input on drive terminal T29 is at 0V. To enable the drive to move to the Off (Ready) state, apply 24V to drive terminal T29.
Off (Ready) 1 The drive is hardware enabled and is waiting for a command to run i.e. Off.
Hand Run 2 The drive is running in Hand mode from a fixed speed reference.
Waking 3 The drive is in the process of waking i.e. the Wake Detect Delay (29.050) is timing.
Pipe Fill 4 The automated pipe filling routine is running.
Auto Run 5 The drive is running in Single Pump control in Auto mode
Auto Run Leader 6 The drive is running in Cascade or Multi-leader control in Auto mode as a Leader.
Auto Run Assist 7 The drive is running in Multi-leader control in Auto mode as an Assist
Pre-sleep 8 The drive is in pre-sleep i.e. the output frequency or speed is less than Sleep Detect Speed Threshold (29.051) and the Sleep Detect Delay (29.052) is counting down. This is shown for a short period when starting in Auto mode while the PID output builds up.
Sleeping 9

The drive is in Auto mode but has gone to sleep. The system enters Sleeping when the motor speed or frequency value satisfies the Sleep Detect Speed Threshold (29.051), if no flow from a flow switch, no flow by software detection or low flow is detected.

This state is entered when External Wake Input (29.186) or External Sleep Input (29.187) = On(1).

When Pump Control Mode (29.011) = Cascade Leader and Assist Control Mode (29.106) = Full I/O OR Run+Ready, and there are no pumps “Ready” as indicated by Assist 1 Ready Input (29.108), Assist 2 Ready Input (29.114), Assist 3 Ready Input (29.160), and Assist 4 Ready Input (29.166) are all set to Off(0), the drive will wait in this state until a pump becomes “Ready”.

Cleaning 10 The drive is running the cleaning or de-ragging routine.
Level Stop 11 The system has stopped due to the high level switch being reached. See Level Switch High Input (29.079). This may be overridden by Hand or Manual Clean operation.
Timer Stop 12 The system has stopped because the timer switch input is not set to On indicating a timer shut-down period. See Time Schedule Run Input Enable (29.055) and Time Schedule Run Input (29.056). This many be overridden by Hand or Manual Clean operation.
Hand Timeout 13 The system was stopped while running in Hand mode after the Hand Mode Timeout (29.017) elapsed. To reset this, deselect and reselect Hand mode.
Over-cycle 14 The system has detected an over-cycle condition. The drive has started too many times in this hour. See Over-cycle Mode (29.127) and Over-cycle Starts Per Hour (29.128).
Fbck Loss Run 15 Analog Input 1 Current Loop Loss (07.028) = On(1) indicating that there is a current loop loss for the main process PID feedback, and PID Feedback Loss Action (29.048) = Fixed Speed where the drive is running with at a fixed speed defined by PID Disabled / Feedback Loss Reference (01.023).
Dry Well Run 16 A dry well low load condition has been detected and the drive is running with a reduced reference as defined by Dry Well Low Load PID Output Reduction (29.060). This state can only be reached when Dry Well Low Load Mode (29.059) = Lower PID Output.
Dry Well Stop 17

A dry well low load condition has been detected and the drive has tripped on Dry Well, where Dry Well Low Load Mode (29.059) = Trip. When this happens the drive will remain stopped in the Dry Well Stop state until the Dry Well Low Load Restart Delay (29.061) has elapsed. When Dry Well Low Load Restart Delay (29.061) is counting down Auto mode isn't available but the user will still be able to activate Hand mode.

If Dry Well Low Load Restart Delay (29.061) = 0 then this state may only be exited if the user deselects and reselects Auto e.g. press the red OFF/Reset button and then press and hold the blue Auto button for 2s.

Auto Stop Assist 18 This indicates that the drive is an assist in a multi-leader system, Auto has been selected but the system leader has not commanded this assist to run.
Trip 19

Indicates when the drive has tripped.

Used to replicate the equivalent standard drive keypad status from Drive Status (10.101) when the software is disabled by setting Pump Software Stop (29.156) = Stop Software.

Under Voltage 20

Indicates when the DC bus voltage is less than the selected under-voltage threshold. See Standard Under Voltage Threshold (06.065), Low Under Voltage Threshold (06.066) and Low Under Voltage Threshold Select (06.067).

Used to replicate the equivalent standard drive keypad status from Drive Status (10.101) when the software is disabled by setting Pump Software Stop (29.156) = Stop Software.

Hand Stop 21 The drive is in Basic mode, Pump Control Mode (29.011) = Basic, Hand mode has been selected via Hand Select Input (29.013) or the Pump Control Word 1 (29.151), Not Stop Input (29.190) = On(1) to permit a run, but a run hasn’t been commanded where Start Input (29.191) = Off(0).
Auto Stop 22 The drive is in Basic mode, Pump Control Mode (29.011) = Basic, Auto mode has been selected via Auto Select Input Pr29.015 or Pump Control Word 1 (29.151), but a run hasn’t been commanded yet by setting Start Input Pr29.191 = On(1). Note that Not Stop Input Pr29.190 may be Off(0) or On(1) when running in Auto in Basic mode since it has no effect.
No Flow Stop 23 The drives PID loop is disabled by PID1 Enable (14.008) = Off(0) or Pump Control Mode (29.011) = Basic, and no flow has been detected from the flow switch input Flow Switch Input (29.066). The drive is latched into No Flow Stop to prevent pump damage by running into a closed discharge valve or a dry well / dry pump. To restart the system deselect and then reselect Auto mode.
Inhibit 24 Used to replicate the equivalent standard drive keypad status from Drive Status (10.101) when the software is disabled by setting Pump Software Stop (29.156) = Stop Software.
Ready 25 Used to replicate the equivalent standard drive keypad status from Drive Status (10.101) when the software is disabled by setting Pump Software Stop (29.156) = Stop Software.
Stop 26 Used to replicate the equivalent standard drive keypad status from Drive Status (10.101) when the software is disabled by setting Pump Software Stop (29.156) = Stop Software.
Scan 27 Used to replicate the equivalent standard drive keypad status from Drive Status (10.101) when the software is disabled by setting Pump Software Stop (29.156) = Stop Software.
Run 28 Used to replicate the equivalent standard drive keypad status from Drive Status (10.101) when the software is disabled by setting Pump Software Stop (29.156) = Stop Software.
Supply Loss 29 Used to replicate the equivalent standard drive keypad status from Drive Status (10.101) when the software is disabled by setting Pump Software Stop (29.156) = Stop Software.
Deceleration 30 Used to replicate the equivalent standard drive keypad status from Drive Status (10.101) when the software is disabled by setting Pump Software Stop (29.156) = Stop Software.
dc Injection 31 Used to replicate the equivalent standard drive keypad status from Drive Status (10.101) when the software is disabled by setting Pump Software Stop (29.156) = Stop Software.
Position 32 Used to replicate the equivalent standard drive keypad status from Drive Status (10.101) when the software is disabled by setting Pump Software Stop (29.156) = Stop Software.
Active 33 Used to replicate the equivalent standard drive keypad status from Drive Status (10.101) when the software is disabled by setting Pump Software Stop (29.156) = Stop Software.
Off 34 Used to replicate the equivalent standard drive keypad status from Drive Status (10.101) when the software is disabled by setting Pump Software Stop (29.156) = Stop Software.
Hand 35 Used to replicate the equivalent standard drive keypad status from Drive Status (10.101) when the software is disabled by setting Pump Software Stop (29.156) = Stop Software.
Auto 36 Used to replicate the equivalent standard drive keypad status from Drive Status (10.101) when the software is disabled by setting Pump Software Stop (29.156) = Stop Software.
Heat 37 Used to replicate the equivalent standard drive keypad status from Drive Status (10.101) when the software is disabled by setting Pump Software Stop (29.156) = Stop Software.
Phasing 38 Used to replicate the equivalent standard drive keypad status from Drive Status (10.101) when the software is disabled by setting Pump Software Stop (29.156) = Stop Software.

The following state diagrams show the interactions between the states.


Parameter29.004  Volume
Short descriptionThe total volume
ModeRFC‑A
Minimum0Maximum2147483647
Default0Units 
Type32 Bit VolatileUpdate Rate4ms
Display FormatStandardDecimal Places0
CodingRW, PR, NC, PT

This indicates the system total volume so far in units defined by Volume Scaling (29.006) e.g. Litres or Gallons. The volume value can be reset by setting Reset Volume Input (29.010) to On(1). To calculate Volume a suitable flow meter must be connected to the drive, as selected by Flow Meter Source Select (29.179).


Parameter29.005  Flow
Short descriptionIndicates the flow rate
ModeRFC‑A
Minimum0.0Maximum100000000.0
Default0.0Units 
Type32 Bit VolatileUpdate Rate4ms
Display FormatStandardDecimal Places1
CodingRW, PR, NC, PT

This indicates the system flow in units defined by Flow Scaling (29.007) e.g. Litres per minute or Gallons per minute. To calculate Flow a suitable flow meter must be connected to the drive, as selected by Flow Meter Source Select (29.179). See Volume (29.004).


Parameter29.006  Volume Scaling
Short descriptionSets the volume scaling in volume per pulse
ModeRFC‑A
Minimum0.000000Maximum1000.000000
Default1.000000Units 
Type32 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places6
CodingRW, PT

When Flow Meter Source Select (29.179) is set to Pulse, this parameter is the scaling factor used to convert the pulsed flow meter count into a volume in a user selected unit e.g. Gallons or Litres. The scaling factor is a volume per flow meter pulse. Many flow meters give a flow rate at a given frequency e.g. 100Hz = 120 litres per second, where this can be converted to a volume per pulse by dividing the flow rate by the frequency e.g. Volume Scaling = 120lps/100Hz = 1.2.

To use a sensor with a flow per minute the scaling must be divided down by 60 (seconds per minute), or 3600 (seconds per hour) for a flow per hour. E.g. for a sensor with a flow rate of 120 litres per minute the volume scaling = 120lpm / (100Hz * 60 seconds per minute) = 0.02.

When Flow Meter Source Select (29.179) is set to Analog, Flow Scaling (29.007) and Volume Scaling (29.006) should be set to 1.000000 unless additional scaling is required.

See Volume (29.004).


Parameter29.007  Flow Scaling
Short descriptionThe Flow scaling in volume/min per pulse
ModeRFC‑A
Minimum0.000000Maximum1000.000000
Default1.000000Units 
Type32 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places6
CodingRW, PT

This is the scaling factor to convert the pulsed flow meter count into a flow rate in a user selected unit e.g. Gallons per minute or Litres per minute. The scaling factor converts the flow rate at maximum frequency to the equivalent flow with a 5s sample rate. Many flow meters give a flow rate at a given frequency e.g. 100Hz = 120 litres per minute, where this can be converted to a flow scale factor by dividing the flow rate by the frequency * 5s e.g. flow Scale Factor = 120lpm/(100Hz*5s) = 0.24.

When Flow Meter Source Select (29.179) is set to Analog, Flow Scaling (29.007) and Volume Scaling (29.006) should be set to 1.000000 unless additional scaling is required.

See Volume (29.004).


Parameter29.008  Flow Meter Pulse Input
Short descriptionA pulsed flow meter is routed to this parameter
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type1 Bit VolatileUpdate Rate4ms
Display FormatStandardDecimal Places0
CodingRW, NC

This is the system input for a pulsed flow meter used to derive Flow and Volume. The maximum input frequency is 100Hz. A digital input with a pulsed flow meter connected should be routed to this parameter.

This input is only used when Flow Meter Source Select (29.179) = Pulse.

See Volume (29.004).


Parameter29.009  Flow Meter Pulse Count
Short descriptionThe total count so far of flow meter pulses
ModeRFC‑A
Minimum0Maximum2147483647
Default0Units 
Type32 Bit Power Down SaveUpdate Rate4ms
Display FormatStandardDecimal Places0
CodingRW, PR, NC, PT

This indicates the total number of flow meter pulses detected so far from the Flow Meter Pulse Input (29.008) when Flow Meter Source Select (29.179) = Pulse.

This indicates the volume calculated so far by integrating the Flow detected from the Flow Meter Analog Input (29.180), after Flow Meter Analog Minimum Scaling (29.181) and Flow Meter Analog Maximum Scaling (29.182) have been applied, when Flow Meter Source Select (29.179) = Analog.

This count can be reset by setting Reset Volume Input (29.010) to On(1). This count is the basis for the Volume calculation so resetting this value will also reset Volume (29.004).

See Volume (29.004).


Parameter29.010  Reset Volume Input
Short descriptionSet to On to reset the volume and flow meter pulse count
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type1 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, NC

When set to On (1), this resets the total number of flow meter pulses detected so far in Flow Meter Pulse Count (29.009) and Volume (29.004).

See Volume (29.004).


Parameter29.011  Pump Control Mode
Short descriptionThis sets the control mode for the drive e.g. Single pump, Cascade etc
ModeRFC‑A
Minimum0Maximum4
Default0Units 
Type8 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, TE, BU

ValueTextDescription
0Single PumpA single drive pump application
1CascadeA single leader drive with up to 2 assist soft starters
2Multi-leaderUp to 3 drive system where the leader role is rotated
3BasicA single pump application with basic controls
4Cascade LeaderA single leader drive with up to 3 assist soft starters. The leader is included in the rotation.

This defines the type of system that the drive is being applied to. The following table shows the options available:

Mode Value Description
Single Pump
 (Simplex)
0

This is for a single pump installation running from a local Hand mode reference or in Auto mode using the main process PID controller to maintain a setpoint e.g. pressure or flow or level. Alternatively, if PID control isn’t required in Auto mode, the drive can run from a fixed speed reference.
Single Pump is the default control mode.

Cascade 
(Duty Assist)
1

This is for a single leader pump drive with up to 2 cascaded assist pumps powered by soft starters. The soft starters are commanded with simple digital I/O from the leader pump drive; the leader drive may require an SI-I/O option to Handle the assist control signals, e.g. when Assist Control Mode (29.106) = Full I/O.

The application may run from a local Hand mode reference or in Auto mode using the main process PID controller to maintain a setpoint e.g. pressure or flow or level. Alternatively, if PID control isn’t required in Auto mode, the drive can run from a fixed speed reference.

Multi-leader (Multiplex) 2

This is for a multi-leader pump installation where up to 3 pumps, controlled by F600 pump drives, are in the system. The role of leader drive is cycled between the pump drives, after a user set time, to even out pump wear. The leader drive requests assist pumps over an Ethernet network; each drive requires an SI-Ethernet option with >=V01.07.03.03 firmware to facilitate the control. The application may run from a local Hand mode reference or in Auto mode using the main process PID controller to maintain a setpoint e.g. pressure or flow or level. Alternatively, if PID control isn’t required in Auto mode, the drive can run from a fixed speed reference.

This has improved redundancy compared to the other modes where any drive can assume the role of leader in the event of a fault. In the event of a faulty PID feedback transducer, the leader can use the feedback from another drive via the Ethernet connection between drives.

Basic 3

This is for a single pump installation where the main system control comes from a PLC or similar controller, such as typical municipality application.

In Basic mode, the user provides a speed reference via PID Disabled / Feedback Loss Reference (01.023), and acceleration rates via General Acceleration Rate (02.011) and General Deceleration Rate (02.021).

Where an analog reference is used to set the speed reference set Analog Input 1 Destination (07.010) to 1.023 to direct Analog input 1 T5 to PID Disabled Reference.

To run the system in Basic mode the Start and Not Stop logic must be satisfied. See Not Stop Input (29.190) and Start Input (29.191) for more details.

To simplify the setup, the following systems are disabled and have no effect when Basic mode is selected:

PID control, PID thresholds, PID feedback loss action, wake and sleep, dry well, low flow, no flow (Software), over-cycle and flow compensation.

Cascade Leader 4

This mode is for a system where up to 4 pumps are controlled by a single F600 where soft starters or contactors power the remaining 3 assist pumps. The soft starters are commanded with simple digital I/O from the leader pump drive; the leader drive may require an SI-I/O option to Handle the assist control signals, e.g. when Assist Control Mode (29.106) = Full I/O.

The leader pump role is rotated among the active pumps in the system when the alternation conditions are met. To accomplish the correct alternation operation, the electrical connections described in the user guide must be followed. In particular,  the activation of the run digital outputs are required to correctly select selectin the leader pump.

The application may run from a local Hand mode reference or in Auto mode using the main process PID controller to maintain a setpoint e.g. pressure or flow or level. Alternatively, if PID control isn’t required in Auto mode, the drive can run from a fixed speed reference.

NOTE: This parameter is only read internally when Hand, Auto and Cleaning are not selected. If Hand or Auto or Cleaning is selected and Pump Control Mode (29.011) is modifed, the previous mode is retained until Hand, Auto and Cleaning are not selected, where the new control mode is used. This is to prevent accidental change of mode during operation.


Parameter29.012  Control Input Mode
Short descriptionSelects how the system will be started and stopped
ModeRFC‑A
Minimum0Maximum3
Default1Units 
Type8 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, TE, BU

ValueTextDescription
0InputHand and Auto switched inputs
1Input & KeypadHand Off and Auto from switched inputs and keypad button press
2Ctrl WrdAll of the main system inputs are handled Control and status words Word
3Ctrl Wrd & InputThe control word and local inputs can be used in parallel for HMIs

This selects how the system will respond to control inputs. The following table shows the options available:

Mode Value Description
Input 0 In this mode the control logic is supplied to local bit type inputs such as Hand Select Input (29.013) or Auto Select Input (29.015). The user is intended to direct digital inputs to all bit type input parameters to be controlled.
Input & Keypad 1

In this mode the control logic to apply either a Hand or Auto or to stop the system can come from either the Keypad HAND, OFF and AUTO buttons or from the digital inputs directed to Hand Select Input (29.013) or Auto Select Input (29.015).

In this mode of control the keypad can be used to start and stop the drive, but will be overridden by Hand Select Input (29.013) or Auto Select Input (29.015) if they are used. When the keypad is overridden, any selections made by it are reset.

To activate Hand or Auto controls on the keypad press and hold the required function key for 2s. The Off key operates with a short press.
All other local bit type control inputs are handled the same as Input.

Ctrl Wrd 2 In this mode, control inputs are exclusively handled by Pump Control Word 1 (29.151) and Pump Control Word 2 (29.152) i.e. the local bit type inputs are ignored. This intended for PLC control, where most PLCs have hardware I/O to Handle devices such as flow switches.
Ctrl Wrd & Input 3 In this mode, control inputs may be asserted via Pump Control Word 1 (29.151) and Pump Control Word 2 (29.152) or by the equivalent local boolean inputs such as the Flow Switch Input (29.066). This intended for HMI control, where most HMIs don’t have hardware I/O, and the F600 Pump drive I/O is used for devices like flow switches, but the HMI is used to select Hand or Auto mode.


Parameter29.013  Hand Select Input
Short descriptionA digital input should be directed to this to select Hand (local/manual) operation
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type1 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, NC

This is the system "Hand" control input used to run the system manually from a switch located close to the pump. This input may be used when Control Input Mode (29.012) = Input or Ctrl Wrd & Input. A digital input with a Hand selection switch connected should be routed to this parameter. The frequency or speed reference can be supplied by an analog input to Hand Mode Analog Reference (01.036) or by a fixed speed reference in Hand Mode Reference (01.022).


Parameter29.015  Auto Select Input
Short descriptionA digital input should be directed to this to select Auto (automatic) operation
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type1 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, NC

This is the system "Auto" control input used to run the system automatically where the system can be controlled by the main process PID, or if the PID is disabled by setting PID1 Enable (14.008) = Off(0), a fixed speed reference set by PID Disabled / Feedback Loss Reference. This input may be used when Control Input Mode (29.012) = Input or Ctrl Wrd & Input. A digital input with an Auto selection switch connected should be routed to this parameter.


Parameter29.016  Hand Mode Reference Select
Short descriptionSelects the reference type used to define the Hand mode speed
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type8 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, TE

ValueTextDescription
0Digital SpeedA digital preset speed reference value
1Analog SpeedAn analog reference speed reference value

This selects where the frequency or speed reference comes from when Hand mode is selected. When set to Digital Speed, Pr1.022 sets the reference. When set to Analog Speed, by default, a 0 to 10V signal is applied to analog input 2 T6. See the following table.

Mode Value Description
Digital Speed 0 In this mode when Hand is selected, the motor speed or frequency reference is provided by Hand Mode Reference (01.022).
Analog Speed 1 In this mode when Hand is selected, the motor speed or frequency reference is provided by a drive analog input Hand Mode Analog Reference (01.036). The default is via T6 Analog input 2.


Parameter29.017  Hand Mode Timeout
Short descriptionSets the number of minutes the hand mode will remain active when >0
ModeRFC‑A
Minimum0.0Maximum25.0
Default0.0Unitsminutes
Type8 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places1
CodingRW, BU

When set to 0.0 minutes, Hand mode timeout is disabled, i.e. the system will run in Hand mode for as long as Hand mode is selected.
When set > 0.0, this sets the time in minutes that Hand mode will be selected for before timing out and stopping the motor, where Operating Status (29.003) changes to Timer Stop. To reset the Hand mode timeout, Hand mode must be deselected.


Parameter29.018  Auto Selected Output
Short descriptionWhen set to "On" indicates that Auto mode is selected
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type1 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, PR, NC

When set to On(1), this indicates that Auto mode has been selected. The following conditions must be met for Auto Selected Output (29.018) to become set to On(1):

When set to Off, Auto mode is not selected.


Parameter29.019  Hand Selected Output
Short descriptionWhen set to "On" indicates that Hand mode is selected
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type1 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, PR, NC

When set to On(1), this indicates that Hand mode has been selected. The following conditions must be met for Hand Selected Output (29.019) to become set to On(1):

When set to Off, Hand mode is not selected.


Parameter29.020  Auto Running Output
Short descriptionAuto mode is selected and the motor is energised
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type1 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, PR, NC

When set to On(1), this indicates that Auto mode is selected and the motor is energised.


Parameter29.021  Auto Operational Output
Short descriptionIndicates that Auto is selected and the drive is in Ready or Run
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type1 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, PR, NC

When set to On(1),  this indicates that Auto mode is selected and the system is sleeping (motor stopped) or running (motor energised).


Parameter29.022  PID Setpoint 0
Short descriptionPID setpoint 0 which is used as the main setpoint, set in user feedback units
ModeRFC‑A
Minimum0.00Maximum327.67
Default0.00Units 
Type16 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places2
CodingRW

PID Setpoint 0 (29.022) is the main process PID setpoint.  PID Setpoint 0 (29.022) is selected by default because the PID setpoint select inputs, PID Setpoint Select Input 0 (29.026) and PID Setpoint Select Input 1 (29.027) are set to Off(0) by default.

The units of this parameter, are defined by the feedback type and scaling, PID Feedback Minimum Scaling (29.031) and PID Feedback Maximum Scaling (29.032), e.g. if the feedback transducer connected to Analog input 1 is a pressure sensor then this is a pressure setpoint with the same scaling. The units shown on the keypad display and the the number of decimal places for this parameter may be selected using PID Unit Select (29.184) and PID Unit Decimal Places (29.185).

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.023  PID Setpoint 1
Short descriptionAn additional PID Setpoint in user feedback units
ModeRFC‑A
Minimum0.00Maximum327.67
Default0.00Units 
Type16 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places2
CodingRW

PID Setpoint 1 (29.023) is an additional setpoint and requires the PID setpoint select inputs, PID Setpoint Select Input 0 (29.026) and PID Setpoint Select Input 1 (29.027) to command it. If PID Setpoint Select Input 0 (29.026) = On(1) and PID Setpoint Select Input 1 (29.027) = Off(0), PID Setpoint 1 (29.023) is selected.

The units of this parameter, are defined by the feedback type and scaling, PID Feedback Minimum Scaling (29.031) and PID Feedback Maximum Scaling (29.032), e.g. if the feedback transducer connected to Analog input 1 is a pressure sensor then this is a pressure setpoint with the same scaling. The units shown on the keypad display and the the number of decimal places for this parameter may be selected using PID Unit Select (29.184) and PID Unit Decimal Places (29.185).

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.024  PID Setpoint 2
Short descriptionAn additional PID Setpoint in user feedback units
ModeRFC‑A
Minimum0.00Maximum327.67
Default0.00Units 
Type16 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places2
CodingRW

PID Setpoint 2 (29.024) is an additional setpoint and requires the PID setpoint select inputs, PID Setpoint Select Input 0 (29.026) and PID Setpoint Select Input 1 (29.027) to command it. If PID Setpoint Select Input 0 (29.026) = Off(0) and PID Setpoint Select Input 1 (29.027) = On(1), PID Setpoint 2 (29.024) is selected.

The units of this parameter, are defined by the feedback type and scaling, PID Feedback Minimum Scaling (29.031) and PID Feedback Maximum Scaling (29.032), e.g. if the feedback transducer connected to Analog input 1 is a pressure sensor then this is a pressure setpoint with the same scaling. The units shown on the keypad display and the the number of decimal places for this parameter may be selected using PID Unit Select (29.184) and PID Unit Decimal Places (29.185).

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.025  PID Setpoint 3
Short descriptionAn additional PID Setpoint in user feedback units
ModeRFC‑A
Minimum0.00Maximum327.67
Default0.00Units 
Type16 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places2
CodingRW

PID Setpoint 3 (29.025) is an additional setpoint and requires the PID setpoint select inputs, PID Setpoint Select Input 0 (29.026) and PID Setpoint Select Input 1 (29.027) to command it. If PID Setpoint Select Input 0 (29.026) = On(1) and PID Setpoint Select Input 1 (29.027) = On(1), PID Setpoint 3 (29.025) is selected.

The units of this parameter, are defined by the feedback type and scaling, PID Feedback Minimum Scaling (29.031) and PID Feedback Maximum Scaling (29.032), e.g. if the feedback transducer connected to Analog input 1 is a pressure sensor then this is a pressure setpoint with the same scaling. The units shown on the keypad display and the the number of decimal places for this parameter may be selected using PID Unit Select (29.184) and PID Unit Decimal Places (29.185).

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.026  PID Setpoint Select Input 0
Short descriptionUsed to select the additional PID setpoints
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type1 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, NC

PID Setpoint Select Input 0 (29.026) is used in combination with PID Setpoint Select Input 1 (29.027) to select the 4 different main process PID setpoints. By default, both inputs are set to Off where PID Setpoint 0 (29.022) is selected. The following table shows how the PID Select inputs may be used to choose which setpoint is active:

PID Setpoint Select Input 0 (29.026) Value PID Setpoint Select Input 1 (29.027)  Value Result
Off(0) Off(0) PID Setpoint 0 (29.022) is selected.
On(1) Off(0) PID Setpoint 1 (29.023) is selected.
Off(0) On(1) PID Setpoint 2 (29.024) is selected.
On(1) On(1) PID Setpoint 3 (29.025) is selected.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.027  PID Setpoint Select Input 1
Short descriptionUsed to select the additional PID setpoints
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type1 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, NC

PID Setpoint Select Input 1 (29.027) is used in combination with PID Setpoint Select Input 0 (29.026) to select the 4 different main process PID setpoints. By default, both inputs are set to Off where PID Setpoint 0 (29.022) is selected. The following table shows how the PID Select inputs may be used to choose which setpoint is active:

PID Setpoint Select Input 0 (29.026) Value PID Setpoint Select Input 1 (29.027)  Value Result
Off(0) Off(0) PID Setpoint 0 (29.022) is selected.
On(1) Off(0) PID Setpoint 1 (29.023) is selected.
Off(0) On(1) PID Setpoint 2 (29.024) is selected.
On(1) On(1) PID Setpoint 3 (29.025) is selected.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.028  PID Selected Setpoint
Short descriptionIndicates the setpoint that was selected by the PID select inputs in user feedback units
ModeRFC‑A
Minimum0.00Maximum327.67
Default0.00Units 
Type16 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places2
CodingRW, PR, NC

This indicates the value of the setpoint selected by PID Setpoint Select Input 0 (29.026) and PID Setpoint Select Input 1 (29.027).

The units of this parameter, are defined by the feedback type and scaling, PID Feedback Minimum Scaling (29.031) and PID Feedback Maximum Scaling (29.032), e.g. if the feedback transducer connected to Analog input 1 is a pressure sensor then this is a pressure setpoint with the same scaling. The units shown on the keypad display and the the number of decimal places for this parameter may be selected using PID Unit Select (29.184) and PID Unit Decimal Places (29.185).

When Flow Compensation Enable is set to On(1), this value is limited to the output of the Flow Compensation interpolation calculation as indicated by Flow Compensation Output Limit.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.029  PID Final Setpoint
Short descriptionIndicates the final PID setpoint after increments and decrements have been applied
ModeRFC‑A
Minimum0.00Maximum327.67
Default0.00Units 
Type16 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places2
CodingRW, PR, NC

This indicates the final value of the setpoint passed to the main process PID reference setpoint PID1 Reference (14.020) shown in feedback units. PID Final Setpoint (29.029) = PID Selected Setpoint (29.028) - No Flow Setpoint Reduction (29.073).

The units of this parameter, are defined by the feedback type and scaling, PID Feedback Minimum Scaling (29.031) and PID Feedback Maximum Scaling (29.032), e.g. if the feedback transducer connected to Analog input 1 is a pressure sensor then this is a pressure setpoint with the same scaling. The units shown on the keypad display and the the number of decimal places for this parameter may be selected using PID Unit Select (29.184) and PID Unit Decimal Places (29.185).

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.030  PID Final Setpoint Percent
Short descriptionIndicates the final setpoint in percent units
ModeRFC‑A
Minimum0.00Maximum100.00
Default0.00Units%
Type16 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places2
CodingRW, PR, NC

This indicates the final value of the setpoint passed to the main process PID reference setpoint PID1 Reference (14.020) in percent units. PID Final Setpoint Percent (29.030) = 100 * (PID Selected Setpoint (29.028) - No Flow Setpoint Reduction (29.073)) / ( PID Feedback Maximum Scaling (29.032) - PID Feedback Minimum Scaling (29.031)).

When PID1 Pre-sleep Boost Level (14.028) is applied during pre-sleep, Sleep Required Output (29.053) = On(1), PID1 Pre-sleep Boost Level (14.028) is added to PID Final Setpoint Percent (29.030) directly.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.031  PID Feedback Minimum Scaling
Short descriptionDefines the minimum scaling value for the analogue PID feedback i.e. the user feedback units
ModeRFC‑A
Minimum0.00Maximum327.67
Default0.00Units 
Type16 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places2
CodingRW

PID Feedback Minimum Scaling (29.031) defines the minimum value for the main process PID feedback provided by a transducer connected to Analog input 1 T5. PID Feedback Minimum Scaling (29.031) is used in combination with PID Feedback Maximum Scaling (29.032) to define to feedback scaling.

The units of this parameter, are defined by the feedback type, e.g. if the feedback transducer connected to Analog input 1 is a pressure sensor then this is a pressure scaling parameter . All of the PID related parameters are scaled within this range e.g. any setpoint or feedback value. The units shown on the keypad display and the the number of decimal places for this parameter may be selected using PID Unit Select (29.184) and PID Unit Decimal Places (29.185).

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.032  PID Feedback Maximum Scaling
Short descriptionDefines the maximum scaling value for the analogue PID feedback i.e. the user feedback units
ModeRFC‑A
Minimum0.01Maximum327.67
Default100.00Units 
Type16 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places2
CodingRW

PID Feedback Maximum Scaling (29.032) defines the maximum value for the main process PID feedback provided by a transducer connected to Analog input 1 T5. PID Feedback Minimum Scaling (29.031) is used in combination with PID Feedback Maximum Scaling (29.032) to define to feedback scaling.

The units of this parameter, are defined by the feedback type, e.g. if the feedback transducer connected to Analog input 1 is a pressure sensor then this is a pressure scaling parameter . All of the PID related parameters are scaled within this range e.g. any setpoint or feedback value. The units shown on the keypad display and the the number of decimal places for this parameter may be selected using PID Unit Select (29.184) and PID Unit Decimal Places (29.185).

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.033  PID Feedback Filter Time Constant
Short descriptionSets the PID feedback filter time constant in seconds
ModeRFC‑A
Minimum0.00Maximum327.67
Default1.00Unitss
Type16 Bit User SaveUpdate Rate4ms
Display FormatStandardDecimal Places2
CodingRW

This is the time constant in seconds for the low pass filter used to condition the value from the feedback transducer connected to Analog input 1 T5.

For a step change in feedback value, after 5x the filter time constant the input and output of the filter will be approximately equal e.g. if the time constant is 1s, after a step change in feedback, after 5s the output will approximately match the input.

The input to the filter is PID Feedback Percent (29.034) and the output from the filter is PID Final Feedback Percent (29.035).

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.034  PID Feedback Percent
Short descriptionThis is the destination for the analog input used for the PID feedback
ModeRFC‑A
Minimum-100.00Maximum100.00
Default0.00Units%
Type16 Bit User SaveUpdate Rate4ms
Display FormatStandardDecimal Places2
CodingRW

This parameter is the destination for the main process PID feedback analog input. by default, Analog input 1 T5 is routed to this parameter. This value is filtered, (see PID Feedback Filter Time Constant (29.033)), where the result of the filter is passed to PID Final Feedback Percent (29.035) which is used as the main process PID feedback value.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.035  PID Final Feedback Percent
Short descriptionThis is the final filtered feedback used by PID
ModeRFC‑A
Minimum-100.00Maximum100.00
Default0.00Units%
Type16 Bit User SaveUpdate Rate4ms
Display FormatStandardDecimal Places2
CodingRW, PR

This parameter is the output of the main process PID feedback filter, (see PID Feedback Filter Time Constant (29.033)), and is routed to the main process PID Feedback reference source in the User PID Controller (14) menu.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.036  PID Final Feedback
Short descriptionThe final PID feedback in user feedback units
ModeRFC‑A
Minimum-327.68Maximum327.67
Default0.00Units 
Type16 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places2
CodingRW, PR, NC

This parameter is the output of the main process PID feedback filter, (see PID Feedback Filter Time Constant (29.033)), and scaled in to feedback units via PID Feedback Minimum Scaling (29.031) and PID Feedback Maximum Scaling (29.032).

PID Final Feedback (29.036) = PID Feedback Minimum Scaling (29.031) + (PID Final Feedback Percent (29.035) * (PID Feedback Maximum Scaling (29.032) - PID Feedback Minimum Scaling (29.031) ) / 100).

The units of this parameter, are defined by the feedback type and scaling, PID Feedback Minimum Scaling (29.031) and PID Feedback Maximum Scaling (29.032), e.g. if the feedback transducer connected to Analog input 1 is a pressure sensor then this is a pressure feedback value with the same scaling. The units shown on the keypad display and the the number of decimal places for this parameter may be selected using PID Unit Select (29.184) and PID Unit Decimal Places (29.185).

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.037  PID Error
Short descriptionIndicates the PID error in user units
ModeRFC‑A
Minimum-327.68Maximum327.67
Default0.00Units 
Type16 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places2
CodingRW, PR

This indicates the main process PID Error in feedback units.

PID Error (29.037) = PID Feedback Minimum Scaling (29.031) + (PID1 Error (14.022) * (PID Feedback Maximum Scaling (29.032) - PID Feedback Minimum Scaling (29.031) ) / 100).

The units of this parameter, are defined by the feedback type and scaling, PID Feedback Minimum Scaling (29.031) and PID Feedback Maximum Scaling (29.032), e.g. if the feedback transducer connected to Analog input 1 is a pressure sensor then this is a pressure error value with the same scaling. The units shown on the keypad display and the the number of decimal places for this parameter may be selected using PID Unit Select (29.184) and PID Unit Decimal Places (29.185).

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.038  PID Software Enable
Short descriptionIndicates when the control software has enabled / disabled the PID
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type1 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, PR, NC, PT

This is used by the Pump software to enable and disable the main process PID (PID1). The PID will be disabled if the system is running in Hand mode, or if the PID feedback has been lost as indicated by Analog Input 1 Current Loop Loss (07.028) in Auto mode and PID Feedback Loss Action (29.048) = Fixed Speed.

The user has the ability to completely disable the main process PID independent of PID Software Enable (29.038) by setting PID1 Enable (14.008) = Off(0). This may be required for systems that require a fixed speed such as a pump system running from level switches where the fixed speed reference is provided by PID Disabled / Feedback Loss Reference (01.023).

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.039  PID Feedback High Alarm Threshold
Short descriptionDefines the upper limit for the PID feedback in user feedback units before an alarm is raised
ModeRFC‑A
Minimum0.00Maximum327.67
Default0.00Units 
Type16 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places2
CodingRW

This defines the threshold above which a main process PID feedback High alarm is given by the PID Feedback High Alarm Output (29.040). 

If PID Feedback High Alarm Threshold (29.039) = 0.00, then the feedback high alarm feature is disabled.

It is possible to rapidly sleep the system in the event of a PID high alarm to preven further feedback increase. See PID Feedback High Sleep Enable (29.188).

The units of this parameter, are defined by the feedback type and scaling, PID Feedback Minimum Scaling (29.031) and PID Feedback Maximum Scaling (29.032), e.g. if the feedback transducer connected to Analog input 1 is a pressure sensor then this is a pressure threshold with the same scaling. The units shown on the keypad display and the the number of decimal places for this parameter may be selected using PID Unit Select (29.184) and PID Unit Decimal Places (29.185).

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.040  PID Feedback High Alarm Output
Short descriptionIndicates when the PID high alarm threshold is reached
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type1 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, PR

This indicates when the PID Feedback High Alarm Threshold (29.039) has been reached or exceed by the PID Final Feedback (29.036).

The function of this parameter is defined by the feedback type and scaling, PID Feedback Minimum Scaling (29.031) and PID Feedback Maximum Scaling (29.032), e.g. if the feedback transducer connected to Analog input 1 is a pressure sensor then this is an over-pressure indication.

Note: this output is held on for a minimum of 1s to allow a HMI to log the Alarm output. This is helpful in situations when PID Feedback High Sleep Enable (29.188) = On(1), where the system will rapidly enter the sleep state in the event that this bit becomes set to 1.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.

 


Parameter29.041  PID Feedback High Trip Threshold
Short descriptionDefines the upper limit for the PID feedback in user feedback units before a trip
ModeRFC‑A
Minimum0.00Maximum327.67
Default0.00Units 
Type16 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places2
CodingRW

When set to 0, the main process PID high trip mechanism is disabled.

When set >0, this defines the threshold above which a PID Feedbk High trip is actioned.

The units of this parameter, are defined by the feedback type and scaling, PID Feedback Minimum Scaling (29.031) and PID Feedback Maximum Scaling (29.032), e.g. if the feedback transducer connected to Analog input 1 is a pressure sensor then this is a pressure threshold with the same scaling. The units shown on the keypad display and the the number of decimal places for this parameter may be selected using PID Unit Select (29.184) and PID Unit Decimal Places (29.185).

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.042  PID Feedback Low Delay
Short descriptionThe filter delay applied when detecting if the feedback is low
ModeRFC‑A
Minimum0.0Maximum6553.5
Default5.0Unitss
Type16 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places1
CodingRW, BU

This defines the continuous time in seconds that the feedback may be low for without actioning a feedback low drive trip. This acts as a filter for transient feedback conditions that prevents false detection of a main process PID feedback low condition.

This parameter is only used when PID Feedback Low Mode (29.043) = Threshold or Bandwidth.

The function of this parameter is defined by the feedback type and scaling, PID Feedback Minimum Scaling (29.031) and PID Feedback Maximum Scaling (29.032), e.g. if the feedback transducer connected to Analog input 1 is a pressure sensor then this is an under-pressure detection delay.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.043  PID Feedback Low Mode
Short descriptionSelects the method used to detect feedback low
ModeRFC‑A
Minimum0Maximum2
Default0Units 
Type8 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, TE, BU

ValueTextDescription
0DisabledPID feedback low detection is disabled
1ThresholdPID feedback low detection by threshold
2BandwidthPID feedback low detection when below the at setpoint bandwidth

PID Feedback Low Mode (29.043) selects which mode to use when generating a feedback low indication and trip. The table below shows the options available:

Mode Value Description
Disabled 0 No feedback low trip.
Threshold 1

If the main process PID feedback, PID Final Feedback (29.036), falls below the PID Feedback Low Threshold (29.044) for PID Feedback Low Delay (29.042) seconds, and the motor output frequency or speed is in the Maximum Drive Reference Band (29.083), then a PID Low drive trip is actioned.

Status indication via PID Feedback Low Output (29.047) is also available.

Bandwidth 2

If the main process PID feedback, PID Final Feedback (29.036), falls below the PID At Setpoint Band (29.045) for PID Feedback Low Delay (29.042) seconds, and the motor output frequency or speed is in the Maximum Drive Reference Band (29.083), then a PID Feedbk Low trip is actioned. The detection band follows the current PID setpoint dynamically.

Status indication via PID Feedback Low Output (29.047) is also available.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.044  PID Feedback Low Threshold
Short descriptionSets the PID feedback low threshold in user feedback units
ModeRFC‑A
Minimum0.00Maximum327.67
Default2.00Units 
Type16 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places2
CodingRW

This defines the PID feedback low threshold, used when PID Feedback Low Mode (29.043) = Bandwidth.

If the main process PID feedback, PID Final Feedback (29.036), falls below the PID Feedback Low Threshold (29.044) for PID Feedback Low Delay (29.042) seconds then a PID Low drive trip is actioned and a PID low indication is given via PID Feedback Low Output (29.047).

The units of this parameter, are defined by the feedback type and scaling, PID Feedback Minimum Scaling (29.031) and PID Feedback Maximum Scaling (29.032), e.g. if the feedback transducer connected to Analog input 1 is a pressure sensor then this is a pressure threshold with the same scaling. The units shown on the keypad display and the the number of decimal places for this parameter may be selected using PID Unit Select (29.184) and PID Unit Decimal Places (29.185).

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.045  PID At Setpoint Band
Short descriptionSets the PID "At Setpoint" band in user feedback units
ModeRFC‑A
Minimum0.00Maximum327.67
Default0.35Units 
Type16 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places2
CodingRW

This defines a symmetrical band around the PID setpoint, PID Final Setpoint (29.029), where the system is considered to be at the setpoint i.e. the top of the band is PID Final Setpoint (29.029) + PID At Setpoint Band (29.045), and the bottom of the band is PID Final Setpoint (29.029) - PID At Setpoint Band (29.045).

If the main process PID feedback, PID Final Feedback (29.036), is within the PID At Setpoint Band (29.045), PID At Setpoint Output (29.046) is set to On(1) indicating that the system is at the setpoint.

Note that No Flow Setpoint Reduction (29.073) must be greater than PID At Setpoint Band (29.045) for the no flow by software detection system to operate correctly.

The units of this parameter, are defined by the feedback type and scaling, PID Feedback Minimum Scaling (29.031) and PID Feedback Maximum Scaling (29.032), e.g. if the feedback transducer connected to Analog input 1 is a pressure sensor then this is a pressure setpoint band with the same scaling. The units shown on the keypad display and the the number of decimal places for this parameter may be selected using PID Unit Select (29.184) and PID Unit Decimal Places (29.185).

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.046  PID At Setpoint Output
Short descriptionIndicates when the PID feedback is at the current setpoint
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type1 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, PR, NC

When set to On(1), this indicates when the main process PID feedback, PID Final Feedback (29.036) is within the PID At Setpoint Band (29.045) indicating that the system is at the setpoint, PID At Setpoint Output (29.046).

This output is used by the no flow by software detection scheme to tell if the setpoint reduction configured by No Flow Setpoint Reduction (29.073) has been reached or not.

When set to Off(0), the system isn't at the setpoint.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.047  PID Feedback Low Output
Short descriptionIndicates when the feedback is outside the At Setpoint window
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type1 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, PR, NC

When set to On(1), this indicates when the main process PID feedback, PID Final Feedback (29.036) is either less than the PID At Setpoint Band (29.045) or the PID Feedback Low Threshold (29.044) indicating that the system is output is lower than the setpoint, PID Final Setpoint (29.029).

When set to Off(0), the system output isn't low.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.048  PID Feedback Loss Action
Short descriptionSets what will happen in the event of a loss of feedback
ModeRFC‑A
Minimum0Maximum2
Default1Units 
Type8 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, TE, BU

ValueText
0Ignore
1Trip
2Fixed Speed

This chooses the action of the software when there is a total loss of PID feedback as indicated by Analog Input 1 Current Loop Loss (07.028) = On(1). The table below shows the options available:

Mode Value Description
Ignore 0 Ignore the feedback loss - do nothing.
Trip 1 Trip the drive, (PID Feedbk Loss).
Fixed Speed 2 Run at a fixed speed defined by PID Disabled / Feedback Loss Reference (01.023).

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.049  Wake Detect Feedback Threshold
Short descriptionSets the system wake threshold in user feedback units
ModeRFC‑A
Minimum0.00Maximum327.67
Default1.00Units 
Type16 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places2
CodingRW

If the PID is running with a normal error response, (PID1 Reference Invert (14.005) and PID1 Feedback Invert (14.006) = Off(0)), Wake Detect Feedback Threshold (29.049) defines the main process PID feedback level, PID Final Feedback (29.036), below which the system will wake when the system is running in Auto mode, and defines the minimum working feedback level for the system. For example, a pumping system with a pressure feedback device gives a high PID output with a low pressure, and a low PID output with high pressure. In this scenario when the feedback is above the setpoint the setpoint the motor reference will reduce down to the minimum. In order to wake the system the PID Feedback must be below the wake threshold.

In a Cascade or Multi-leader system the Wake Detect Feedback Threshold (29.049) is used in combination with the Add Assist Band (29.123) to decide when to start an assist i.e. both the add assist and wake thresholds must be satisfied to start an assist.

 

If the PID is running with an inverse error response, (PID1 Reference Invert (14.005) and PID1 Feedback Invert (14.006) = On(1)), Wake Detect Feedback Threshold (29.049) defines the main process PID feedback level, PID Final Feedback (29.036), above which the system will wake when the system is running in Auto mode. For example, cooling system with a temperature feedback device gives a high PID output with a high temperature, and a low PID output with low temperature. In this scenario when the feedback is below the setpoint the motor reference will reduce down to the minimum. In order to wake the system the PID Feedback must be above the wake threshold.

The units of this parameter, are defined by the feedback type and scaling, PID Feedback Minimum Scaling (29.031) and PID Feedback Maximum Scaling (29.032), e.g. if the feedback transducer connected to Analog input 1 is a pressure sensor then this is a pressure threshold with the same scaling. The units shown on the keypad display and the the number of decimal places for this parameter may be selected using PID Unit Select (29.184) and PID Unit Decimal Places (29.185).

Note that if the main process PID has been disabled via PID1 Enable (14.008), then the wake threshold is ignored and the system will wake when started in Auto mode.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.050  Wake Detect Delay
Short descriptionSets the system wake detection delay time
ModeRFC‑A
Minimum0.0Maximum6553.5
Default5.0Unitss
Type16 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places1
CodingRW, BU

This defines the continuous time in seconds that the main process PID feedback, PID Final Feedback (29.036), must be below the Wake Detect Feedback Threshold (29.049) before the system is automatically started, with the default PID response. Wake Detect Delay (29.050) filters out any intermittent wake conditions.

Note that if the main process PID has been disabled via PID1 Enable (14.008), then the wake threshold is ignored and the system will wake when started in Auto mode.

See Wake Detect Feedback Threshold (29.049).

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.051  Sleep Detect Speed Threshold
Short descriptionSets the speed threshold where the system should go to sleep
ModeRFC‑A
Minimum0.0Maximum3000.0
Default750.0Units 
Type32 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places1
CodingRW

This defines the drive output frequency or speed below which the system will sleep. Note that Sleep Detect Speed Threshold (29.051) must be set >= Positive Minimum Reference Clamp (01.004), so that the lead drive and assists will sleep in Auto mode.

If the system must never automatically sleep but still control using the PID then set Sleep Detect Speed Threshold (29.051) to a lower value than Positive Minimum Reference Clamp (01.004). Note that other conditions like Dry Well Low Load or No Flow can still stop the system automatically.

The system will tend to reach this threshold if there is no output demand from the pump e.g. in a pump system if a pump output valve is closed the motor speed will drop because the main process PID can reach the setpoint with a reduced speed where the system will enter this threshold.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.052  Sleep Detect Delay
Short descriptionSets the system sleep detection delay time
ModeRFC‑A
Minimum0.0Maximum6553.5
Default5.0Unitss
Type16 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places1
CodingRW, BU

This defines the continuous time in seconds that the motor frequency or speed must be below the Sleep Detect Speed Threshold (29.051) before the system is automatically stopped. Sleep Detect Delay (29.052) filters out any intermittent sleep conditions.

See Sleep Detect Speed Threshold (29.051).

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.053  Sleep Required Output
Short descriptionIndicates when the sleep threshold has been reached and the delay timer is counting down
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type1 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, PR, NC

This indicates when the motor frequency or speed is below the Sleep Detect Speed Threshold (29.051) and the Sleep Detect Delay (29.052) is timing down indicating that a sleep is required i.e. pre-sleep.

See Sleep Detect Speed Threshold (29.051).

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.054  Sleep Active Output
Short descriptionIndicates when the drive has entered sleep mode
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type8 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, PR, TE, NC

ValueText
0Off
1On

This indicates when the motor frequency or speed was below the Sleep Detect Speed Threshold (29.051) and the Sleep Detect Delay (29.052) has elapsed and the system is sleeping.

See Sleep Detect Speed Threshold (29.051).

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.055  Time Schedule Run Input Enable
Short descriptionEnables the time schedule run input function
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type1 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW

When set to On(1), Time Schedule Run Input (29.056) is enabled. To run the system in Auto Time Schedule Run Input (29.056) must be set to On(1), and to stop the system Time Schedule Run Input (29.056) must be set to Off(0). This feature is intended to be operated by a clock such as the one provided by a KI-HOA Keypad RTC keypad, where timer 1 in the User Functions 1 (09) menu may be used to define on and off periods for the system e.g. for an irrigation pump it may be desirable to run the pump during the day only. By default, the output of timer 1, Timer 1 Output (09.042), is routed to the Time Schedule Run Input (29.056) using Timer 1 Destination (09.043).

When set to Off(0), Time Schedule Run Input (29.056) is disabled and has no effect on the system.


Parameter29.056  Time Schedule Run Input
Short descriptionOff = Stop, On = Run. Connect to menu 9 timer or external timer unit
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type8 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, TE, NC

ValueText
0Off
1On

To use this input Time Schedule Run Input Enable (29.055) must be set to On(1).

When set to On(1), the system will be permitted to run in Auto mode.

When set to Off(0), the system will be stopped in Auto mode.

Time Schedule Run Input (29.056) has no effect on the operation of hand mode.

This feature is intended to be operated by a clock such as the one provided by a KI-HOA Keypad RTC keypad, where timer 1 in the User Functions 1 (09) menu may be used to define on and off periods for the system e.g. for an irrigation pump it may be desirable to run the pump during the day only. By default, the output of timer 1, Timer 1 Output (09.042), is routed to the Time Schedule Run Input (29.056) using Timer 1 Destination (09.043).

See Time Schedule Run Input Enable (29.055).


Parameter29.057  Dry Well Low Load Detection Threshold Percent
Short descriptionSets the percentage PID output level below which Dry Well is detected
ModeRFC‑A
Minimum0.0Maximum100.0
Default1.0Units%
Type16 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places1
CodingRW, BU

This defines the load percentage below which a dry well low load condition is detected. Dry Well Low Load Detection Threshold Percent (29.057) is compared against Percentage Load (04.020). To complete the dry well low load detection logic the motor frequency or speed must be within the Maximum Drive Reference Band (29.083). Note that Percentage Load (04.020) must not be 0% in order to activate the dry well feature i.e. a motor must be connected.

Note that if the main process PID has been disabled via PID1 Enable (14.008), then Dry Well Low Load detection is internally disabled.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.058  Dry Well Low Load Detection Delay
Short descriptionSets the dry well / low load detection delay
ModeRFC‑A
Minimum0.0Maximum6553.5
Default5.0Unitss
Type16 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places1
CodingRW, BU

This defines the continuous time in seconds that the load level must be below the Dry Well Low Load Detection Threshold Percent (29.057) and the motor frequency or speed must be within the Maximum Drive Reference Band (29.083) to detect a dry well low load condition. Dry Well Low Load Detection Delay (29.058) filters out any intermittent Dry Well Low Load conditions.

Note that if the main process PID has been disabled via PID1 Enable (14.008), then Dry Well Low Load detection is internally disabled.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.059  Dry Well Low Load Mode
Short descriptionSelects the action taken when dry well / low load is detected
ModeRFC‑A
Minimum0Maximum3
Default0Units 
Type8 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, TE, BU

ValueText
0Disabled
1Alarm Only
2Trip
3Lower PID Output

This defines the Dry Well Low Load system will operate. The following options are available:

Mode Value Description
Disabled 0 The Dry Well Low Load detection system is disabled.
Alarm Only 1 If a Dry Well Low Load condition is detected, an alarm is raised (Dry Well Low Load Alarm Output (29.062) = On(1)).
Trip 2 If a Dry Well Low Load condition is detected, a Dry Well trip is actioned..
Lower PID Output 3 If a Dry Well Low Load condition is detected, the PID output is lowered by the Dry Well Low Load PID Output Reduction (29.060) value thereby limiting potential damage to the pump. When the load value is above the Dry Well Low Load Detection Threshold Percent (29.057), the PID output is restored. Operating Status (29.003) = Dry Well Run when the PID output has been reduced due to a dry well condition.

If a Dry Well condition is detected in a Cascade system, Pump Control Mode (29.011) = Cascade, the Soft Starters will be stopped to prevent pump wear. The Soft Starters will automatically restart when the Dry Well condition has finished.

Note that if the main process PID has been disabled via PID1 Enable (14.008), then Dry Well Low Load detection is internally disabled.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.060  Dry Well Low Load PID Output Reduction
Short descriptionA percentage to lower the PID output by during Dry Well / Low Load
ModeRFC‑A
Minimum0.00Maximum100.00
Default50.00Units%
Type16 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places2
CodingRW

When Dry Well Low Load Mode (29.059) = Lower PID Output, if a Dry Well Low Load condition is detected, the PID output is lowered by the Dry Well Low Load PID Output Reduction (29.060) value thereby limiting potential damage to the pump. When the load value is above the Dry Well Low Load Detection Threshold Percent (29.057), the PID output is restored.

Operating Status (29.003) = Dry Well Run when Dry Well Low Load PID Output Reduction (29.060) has been used to reduce the PID output due to a dry well condition.

Note that if the main process PID has been disabled via PID1 Enable (14.008), then Dry Well Low Load detection is internally disabled.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.061  Dry Well Low Load Restart Delay
Short descriptionWhen the drive trips due to low load this is the minimum restart time
ModeRFC‑A
Minimum0.0Maximum6553.5
Default5.0Unitss
Type16 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places1
CodingRW, BU

When Dry Well Low Load Restart Delay (29.061) = 0 and a dry well is detected, the drive will trip on Dry Well, and then enter the Dry Well Stop state. The user must deselect Auto mode to leave the Dry Well Stop state, after which the pump drive may be restarted by selecting Auto mode again. This forces the user to reset the system when the liquid supply is back thereby preventing damage by running the pump dry.

When Dry Well Low Load Restart Delay (29.061) is > 0.0, this defines the minimum time in seconds after the drive has been tripped due to a Dry Well Low Load condition before it can be restarted. This prevents the system from automatically resetting and attempting to run again without there being sufficient time to allow the well or tank to fill again. When Dry Well Low Load Restart Delay (29.061) is counting down Auto mode isn't available but the user will still be able to activate Hand mode.

This is only used when Dry Well Low Load Mode (29.059) = Trip.

Note that if the main process PID has been disabled via PID1 Enable (14.008), then Dry Well Low Load detection is internally disabled.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.062  Dry Well Low Load Alarm Output
Short descriptionIndicates dry well / low load
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type8 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, PR, TE, NC

ValueText
0Off
1On

When set to On(1), this indicates when a Dry Well Low Load condition has been detected.

Note that if the main process PID has been disabled via PID1 Enable (14.008), then Dry Well Low Load detection is internally disabled.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.063  Low Flow Meter Stop Threshold
Short descriptionSets the low flow threshold from a pulsed flow meter
ModeRFC‑A
Minimum0.0Maximum214748364.7
Default0.0Units 
Type32 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places1
CodingRW

This defines the threshold below which the system will stop due to a low flow condition, detected using the pulsed flow meter feedback. This is set in the units defined by the Flow Scaling (29.007).

A suitable pulsed output flow meter must be connected to a digital input routed to the Flow Meter Pulse Input (29.008) to allow the Low Flow functionality to operate.

In the event that a low flow is detected, Operating Status (29.003) will transition to Sleeping.

See Volume (29.004).

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.064  Low Flow Meter Stop Delay
Short description0 = Disable Low Flow. >0 Sets the low flow detection time from a flow meter
ModeRFC‑A
Minimum0.0Maximum6553.5
Default5.0Unitss
Type16 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places1
CodingRW, BU

When set to 0, the low flow stop feature is disabled.

When set to >0, the low flow stop feature is enabled.

This defines the continuous time in seconds that the Flow (29.005) must be below the Low Flow Meter Stop Threshold (29.063) to detect a low flow condition. Low Flow Meter Stop Delay (29.064) filters out any intermittent Low Flow conditions.

A suitable pulsed output flow meter must be connected to a digital input routed to the Flow Meter Pulse Input (29.008) to allow the Low Flow functionality to operate.

See Volume (29.004).

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.065  Low Flow Meter Stop Output
Short descriptionIndicates when a low flow from a pulse flow meter has been detected
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type8 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, PR, TE, NC

ValueText
0Off
1On

This indicates when a Low Flow meter stop has been actioned. This happens when the Flow (29.005) is below the Low Flow Meter Stop Threshold (29.063) and the Low Flow Meter Stop Delay (29.064) has elapsed.

A suitable pulsed output flow meter must be connected to a digital input routed to the Flow Meter Pulse Input (29.008) to allow the Low Flow functionality to operate.

See Volume (29.004).

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.066  Flow Switch Input
Short descriptionOff = No Flow, On = Flow .A digital input should be directed to this to input a flow switch.
ModeRFC‑A
Minimum0Maximum1
Default1Units 
Type8 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, TE, NC

ValueText
0Off
1On

This is the input for a flow switch where Off(0) = No flow, On(1) = Flow. A digital input with a flow switch connected should be routed to this parameter. This input is used to detect when the system should stop due to no flow and to terminate the automatic pipe filling routine when flow is detected; see No Flow Switch Delay (29.067) and Pipe Fill Mode (29.075).

Where a flow switch is not fitted, set Flow Switch Input (29.066) to On(1) and perform a drive parameter save to prevent a false no flow stop.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), if no flow from a flow switch is required, the pipe fill feature must be used to prime the pump and pipe system to prevent false no flow stops. It is recommended to set Pipe Fill Mode (29.075) = Flow Switch, and cofigure the remaining pipe fill parameters to suit the system. When the pipe fill routine is running, no flow detection from the flow switch is disabled.


Parameter29.067  No Flow Switch Delay
Short descriptionSets the day before detecting a No Flow from a connected flow switch
ModeRFC‑A
Minimum0.0Maximum6553.5
Default5.0Unitss
Type16 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places1
CodingRW, BU

This defines the continuous time in seconds that the Flow Switch Input (29.066) must be set to Off(0) to detect a no flow condition. No Flow Switch Delay (29.067) filters out any intermittent No Flow conditions.

A suitable flow switch must be connected to a digital input routed to the Flow Switch Input (29.066) to allow the No Flow by switch functionality to operate.

If a flow switch is fitted then no flow by software detection is not required. The pump will be protected from running into a closed output using the flow switch.

In the event that a no flow is detected, Operating Status (29.003) will transition to Sleeping and the motor will stop.

See Flow Switch Input (29.066).


Parameter29.068  No Flow Switch Output
Short descriptionIndicates when no flow has been detect from a connected flow switch
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type8 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, PR, TE, NC

ValueText
0Off
1On

This indicates when a No Flow detection from a flow switch has been detected. This happens when the Flow Switch Input (29.066) = Off(0) for No Flow Switch Delay (29.067) seconds.

A suitable flow switch must be connected to a digital input routed to the Flow Switch Input (29.066) to allow the No Flow by switch functionality to operate.

In the event that a no flow is detected, Operating Status (29.003) will transition to Sleeping and the motor will stop.

See Flow Switch Input (29.066).


Parameter29.069  No Flow Detection Threshold
Short descriptionSets the speed / frequency below which no flow will be detected
ModeRFC‑A
Minimum0.0Maximum3000.0
Default0.0Units 
Type32 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places1
CodingRW

When No Flow Detection Threshold (29.069) is > 0, software detection of no flow is enabled. This defines the frequency or speed threshold below which software based no flow is detected. This must be set to the greater of the Positive Minimum Reference Clamp (01.004) OR the Sleep Detect Speed Threshold (29.051) + No Flow Detection Band (29.070). In the event of a closed pump discharge, the main process PID feedback will rise causing the motor frequency or speed to dip below this level.

When No Flow Detection Threshold (29.069) = 0, software detection of no flow is disabled.

Note that if the main process PID has been disabled via PID1 Enable (14.008), then then no flow detection when running in Auto mode is disabled.

In the event that a no flow is detected, Operating Status (29.003) will transition to Sleeping and the motor will stop.

No flow by software detection is particularly helpful when controlling pumps that have a flat pressure to speed relationship at maximum pressure. This is when changes in speed result in little or no change in pressure (head), where the discharge valve may be closed slowly resulting in no flow, but the pressure feedback does not change, which may leave the pump drive running. In this scenario, a PID controller alone is unable to regulate the pump speed due to the static feedback response. The following diagram illustrates the operating region where the no flow by software detection system may be helpful. 

The No Flow by software detection scheme is made up of four stages:

  1. Is the motor frequency or speed is < No Flow Detection Threshold (29.069)? If yes, move to the next step.
  2. Is the motor frequency or speed within the No Flow Detection Band (29.070) for No Flow Detection Delay (29.071) seconds? If yes, move to the next step.
  3. Reduce the main process PID setpoint by No Flow Setpoint Reduction (29.073) and wait for the No Flow Setpoint Settling Delay (29.072) to elapse. Is the PID is unable to follow the new setpoint? If yes, move to the next step.
  4. Stop the system and set No Flow Output (29.074) to On(1). If the feedback is within the PID At Setpoint Output (29.046) window, move to step 1.

Note that in a Multi-leader or Cascade system that the system must have removed all of the assists before the no flow by software detection system will operate. It is therefore essential that the sleep threshold is set higher than the frequency or speed that the system settles at when the output valve is closed, so any connected assists will be removed from operation. This is particularly important when running at the maximum pressure the pump is rated for and the output valve is closed slowly.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.070  No Flow Detection Band
Short descriptionSets the speed band below the threshold where no flow is detected
ModeRFC‑A
Minimum0.0Maximum3000.0
Default150.0Units 
Type32 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places1
CodingRW

This defines the frequency or speed band used by the software no flow detection scheme. It is recommended to set this to 10% of the Maximum Reference Clamp (01.006). In the event of a closed pump discharge, the PID feedback will rise causing the motor frequency or speed to dip into this band.

This is only used when No Flow Detection Threshold (29.069) is > 0. See No Flow Detection Threshold (29.069) for details on the no flow by software detection process.

Note that if the main process PID has been disabled via PID1 Enable (14.008), then then no flow detection when running in Auto mode is disabled.

In the event that a no flow is detected, Operating Status (29.003) will transition to Sleeping and the motor will stop.

See No Flow Detection Threshold (29.069).

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.071  No Flow Detection Delay
Short descriptionA time that the no flow condition must be detected for before taking action.
ModeRFC‑A
Minimum0.0Maximum6553.5
Default5.0Unitss
Type16 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places1
CodingRW, BU

This defines the continuous time in seconds that the motor frequency or speed must be below the No Flow Detection Threshold (29.069) to complete stage 1 of the no flow by software detection scheme. No Flow Detection Delay (29.071) filters out any intermittent No Flow conditions.

This is only used when No Flow Detection Threshold (29.069) is > 0. See No Flow Detection Threshold (29.069) for details on the no flow by software detection process.

Note that if the main process PID has been disabled via PID1 Enable (14.008), then no flow detection when running in Auto mode is disabled.

In the event that a no flow is detected, Operating Status (29.003) will transition to Sleeping and the motor will stop.

See No Flow Detection Threshold (29.069).

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.072  No Flow Setpoint Settling Delay
Short descriptionA settling delay applied after the setpoint had been reduced by the no flow software detection
ModeRFC‑A
Minimum0.0Maximum6553.5
Default1.0Unitss
Type16 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places1
CodingRW, BU

This defines the continuous time in seconds that the no flow by software detection scheme will wait after applying the No Flow Setpoint Reduction (29.073) before checking if the main process PID is able to track the change in setpoint. If the main process PID isn't able to track the change in setpoint a no flow by software detection stop is actioned and No Flow Output (29.074) is set to On(1).

This is only used when No Flow Detection Threshold (29.069) is > 0. See No Flow Detection Threshold (29.069) for details on the no flow by software detection process.

Note that if the main process PID has been disabled via PID1 Enable (14.008), then then no flow detection when running in Auto mode is disabled.

In the event that a no flow is detected, Operating Status (29.003) will transition to Sleeping and the motor will stop.

See No Flow Detection Threshold (29.069).

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.073  No Flow Setpoint Reduction
Short descriptionUsed to reduce the setpoint in user feedback units when no flow is detected
ModeRFC‑A
Minimum0.00Maximum2.55
Default0.06Units 
Type8 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places2
CodingRW, BU

This defines the main process PID setpoint reduction value used in stage 2 of detecting no flow by software.  After applying the No Flow Setpoint Reduction (29.073) and waiting for the No Flow Setpoint Settling Delay (29.072) to elapse, the software will check to see if the main process PID hasn't been able to track the change in setpoint; if it hasn't then software no flow is detected. and the system will stop.

The drive checks if the PID has followed the No Flow Setpoint Reduction (29.073) by checking if PID At Setpoint Output (29.046) = On(1). Note that No Flow Setpoint Reduction (29.073) must be greater than PID At Setpoint Band (29.045) for the no flow by software detection system to operate correctly.

This is only used when No Flow Detection Threshold (29.069) is > 0. See No Flow Detection Threshold (29.069) for details on the no flow by software detection process.

Note that if the main process PID has been disabled via PID1 Enable (14.008), then then no flow detection when running in Auto mode is disabled.

The units of this parameter, are defined by the feedback type and scaling, PID Feedback Minimum Scaling (29.031) and PID Feedback Maximum Scaling (29.032), e.g. if the feedback transducer connected to Analog input 1 is a pressure sensor then this is a pressure setpoint reduction with the same scaling. The units shown on the keypad display and the the number of decimal places for this parameter may be selected using PID Unit Select (29.184) and PID Unit Decimal Places (29.185).

In the event that a no flow is detected, Operating Status (29.003) will transition to Sleeping and the motor will stop.

See No Flow Detection Threshold (29.069).

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.074  No Flow Output
Short descriptionIndicates when the no flow software has detected a no flow
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type8 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, PR, TE, BU

ValueText
0Off
1On

When set to On(1), this indicates that the system has stopped due to software based no flow detection. The No Flow by software detection scheme is made up of four stages:

  1. Is the motor frequency or speed is < No Flow Detection Threshold (29.069)? If yes, move to the next step.
  2. Is the motor frequency or speed within the No Flow Detection Band (29.070) for No Flow Detection Delay (29.071) seconds? If yes, move to the next step.
  3. Reduce the main process PID setpoint by No Flow Setpoint Reduction (29.073) and wait for the No Flow Setpoint Settling Delay (29.072) to elapse. Is the PID is unable to follow the new setpoint? If yes, move to the next step.
  4. Stop the system and set No Flow Output (29.074) to On(1). If the feedback is within the PID At Setpoint Output (29.046) window, move to step 1.

Note that if the main process PID has been disabled via PID1 Enable (14.008), then then no flow detection when running in Auto mode is disabled.

In the event that a no flow is detected, Operating Status (29.003) will transition to Sleeping and the motor will stop.

See No Flow Detection Threshold (29.069).

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.075  Pipe Fill Mode
Short descriptionUsed to disable pipe fill or choose the feedback type that indicates when the pipe is full
ModeRFC‑A
Minimum0Maximum2
Default0Units 
Type8 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, TE, BU

ValueTextDescription
0DisabledPipe filling is disabled
1Feedback LevelFill to a user defined feedback level
2Flow SwitchFill until the flow switch indicates flow

This defines the operating mode of the automated pipe fill routine. The following options are available:

Mode Value Description
Disabled 0 The pipe fill routine is disabled.
Feedback Level 1 Pipe Fill Reference (01.024) will be applied until Pipe Fill Threshold (29.076) is reached by the main process PID feedback. In the event that the Pipe Fill Threshold (29.076) isn't reached the Pipe Fill Maximum Time (29.077) will elapse stopping the automatic pipe filling routine. Pipe filling happens every time the system wakes.
Flow Switch 2 Pipe Fill Reference (01.024) will be applied until the Flow Switch Input (29.066) = On(1). In the event that the Flow Switch Input (29.066) isn't set to On(1) the Pipe Fill Maximum Time (29.077) will elapse stopping the automatic pipe filling routine. Pipe filling happens every time the system wakes.

The pipe fill routine is intended for pumping systems that have to purge large volumes of air from the water distribution system, on start up, such as an agricultural irrigation system.

The feature may also be used to start submersible pumps that need to be run rapidly up to around 80% of their rated speed for a fixed time before switching to PID control, or to simply preset the output of the PID to reduce overshoot on wake. To do this:



When basic mode is selected, (Pump Control Mode (29.011) = Basic), if no flow from a flow switch is required, the pipe fill feature must be used to prime the pump and pipe system to prevent false no flow stops. It is recommended to set Pipe Fill Mode (29.075) = Flow Switch, and cofigure the remaining pipe fill parameters to suit the system. When the pipe fill routine is running, no flow detection from the flow switch is disabled.


Parameter29.076  Pipe Fill Threshold
Short descriptionSets the feedback threshold in user feedback units when the pipe is considered filled
ModeRFC‑A
Minimum0.00Maximum327.67
Default0.00Units 
Type16 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places2
CodingRW

This defines main PID feedback threshold above which the pipe is considered to be filled when Pipe Fill Mode (29.075) = Feedback Level. Pipe Fill Threshold (29.076) is compared against PID Final Feedback (29.036).

The units of this parameter, are defined by the feedback type and scaling, PID Feedback Minimum Scaling (29.031) and PID Feedback Maximum Scaling (29.032), e.g. if the feedback transducer connected to Analog input 1 is a pressure sensor then this is a pressure threshold with the same scaling. The units shown on the keypad display and the the number of decimal places for this parameter may be selected using PID Unit Select (29.184) and PID Unit Decimal Places (29.185).

See Pipe Fill Mode (29.075).


Parameter29.077  Pipe Fill Maximum Time
Short descriptionThis defines the maximum time that the pipe fill function will run for
ModeRFC‑A
Minimum0.0Maximum6553.5
Default0.0Unitss
Type16 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places1
CodingRW, BU

This defines the maximum time in seconds that the pipe filling routine will run for in the event that pipe filled isn't detected by either feedback detection or flow switch detection.

See Pipe Fill Mode (29.075).


Parameter29.078  Pipe Fill Done Output
Short descriptionIndicates when the pipe fill operation has completed
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type8 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, PR, TE, NC

ValueText
0Off
1On

When set to On(1), this indicates that the pipe filling routine has completed.

When set to Off(0), this indicates that the pipe filling routine is not enabled via Pipe Fill Mode (29.075) or pipe filling has not been completed.

See Pipe Fill Mode (29.075).


Parameter29.079  Level Switch High Input
Short descriptionA digital input from a tank level high switch / probe should be directed to this parameter
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type8 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, TE, NC, BU

ValueText
0Off
1On

This is the input for a tank level high probe or switch where Off(0) = not at high level, On(1) = at the high level and the system must stop. A digital input with a tank high level probe or switch connected should be routed to Level Switch High Input (29.079).

If Level Switch High Input (29.079) and Level Switch Low Input (29.080) = On(1) the high switch action has priority and the system will stop.

 


Parameter29.080  Level Switch Low Input
Short descriptionA digital input from a tank level low switch / probe should be directed to this parameter
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type8 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, TE, NC, BU

ValueText
0Off
1On

This is the input for a tank high level low probe or switch where Off(0) = not at low level, On(1) = at the low level, where if Level Switch Mode (29.082) = High Low Toggle the system will start. A digital input with a tank level low probe or switch connected should be routed to Level Switch Low Input (29.080).

If Level Switch High Input (29.079) and Level Switch Low Input (29.080) = On(1) the high switch action has priority and the system will stop. The low level switch is only active when running in Auto mode.

This is intended to be used in a pumping system where the PID is not in use, PID1 Enable (14.008) = Off(0), and the system must fill a tank until the high level switch is reached, and then let the level fall until the low level switch is reached where the system will start again. If PID1 Enable (14.008) = On(1), then the system must hit the low level switch and meet the wake criteria e.g. Wake Detect Feedback Threshold (29.049).


Parameter29.081  Level Switch Hold Delay
Short descriptionThis defines the delay after level high / low has been detected to maintain that condition
ModeRFC‑A
Minimum0.0Maximum6553.5
Default5.0Unitss
Type16 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places1
CodingRW, BU

This defines the minimum time in seconds for either a high or low level switch activation to be maintained for regardless of the state of the Level Switch High Input (29.079) or Level Switch Low Input (29.080). A fixed 500ms switch debounce delay is added when confirming a level high or low switch activation.


Parameter29.082  Level Switch Mode
Short descriptionSelects the level switch operating mode
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type8 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, TE, BU

ValueTextDescription
0High OnlyOnly the high switch is active, shutting down the pump if it is reached
1High Low ToggleThe high and low switches are active toggling the system run

This defines the operating mode of the level switches. The following options are available:

Mode Value Description
High Only 0 When the Level Switch High Input (29.079) is set to On(1) the system will stop. This only happens when running in Auto mode,  Hand mode and Cleaning are not affected. The Level Switch Low Input (29.080) is not used.
High Low Toggle 1 The Level Switch Low Input (29.080) is enabled where if this input = On(1) the system will run until the Level Switch High Input (29.079) = On(1) when the system stops. The level will rise and fall automatically between these two limits. The low input and high input logic level does not need to be maintained.


Parameter29.083  Maximum Drive Reference Band
Short descriptionSets the maximum drive reference band below the maximum
ModeRFC‑A
Minimum0.0Maximum3000.0
Default30.0Units 
Type32 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places1
CodingRW

This defines the band below the Maximum Reference Clamp (01.006) where the drive is considered to be at the maximum reference as indicated by At Maximum Drive Reference  (29.084). This can be used to tell if the drive has reached full capacity while trying to achieve the main process PID setpoint.

This is used as part of the Dry Well Low Load detection scheme; see Dry Well Low Load Detection Delay (29.058).


Parameter29.084  At Maximum Drive Reference
Short descriptionIndicates when the drive has reached the maximum reference
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type8 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, PR, TE, NC, BU

ValueText
0Off
1On

When Set to On(1), this indicates that the drive has entered the Maximum Drive Reference Band (29.083)  reached the maximum reference possible where the drive is considered to be at full capacity while trying to achieve the main process PID setpoint.

This indication is used as part of the Dry Well Low Load detection scheme; see Dry Well Low Load Detection Delay (29.058).


Parameter29.085  External Pump Fault Input
Short descriptionA digital input should be routed to this to stop the pump in the event of an external fault
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type8 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, TE, NC, BU

ValueText
0Off
1On

This is the input for an external pump fault indication where Off(0) = no external fault, On(1) = external fault where the drive will trip on Ext Pump Fault. A digital input with an external pump fault signal connected should be routed to External Pump Fault Input (29.085). This is intended to cause the system to stopthe sytem with a trip in the event of a 3rd party device indicating that it is faulty.


Parameter29.086  Motor Thermal Protection Input
Short descriptionOff = Too Hot, On = OK
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type8 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, TE, NC, BU

ValueText
0Off
1On

Motor Thermal Protection Enable (29.087) must be set to On(1) to enable the Motor Thermal Protection Input (29.086). If Motor Thermal Protection Enable (29.087) = Off(0), Motor Thermal Protection Input (29.086) is disabled. 

This is the input for a motor over-temperature switch, e.g. a bimetallic thermal switch where On(1) = Motor temperature is OK, Off(0) = Motor temperature is too high where the drive will trip on Motor Over Temp. A digital input with a motor over-temperature switch connected should be routed to Motor Thermal Protection Input (29.086).


Parameter29.087  Motor Thermal Protection Enable
Short descriptionOff = Disabled, On = Enabled. Selects whether the motor temperature monitoring input is enabled or not
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type1 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW

When set to On(1), to the Motor Thermal Protection Input (29.086) is enabled.

When set to Off(0), to the Motor Thermal Protection Input (29.086) is disabled.

See Motor Thermal Protection Input (29.086).


Parameter29.088  Clean Manual Input
Short descriptionWhen set to On, this runs cleaning / de-ragging profile
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type8 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, TE, NC, BU

ValueText
0Off
1On

When set to On(1) and provided Hand Select Input (29.013) = Off(0) and Auto Select Input (29.015) = Off(0), this will manually start a cleaning cycle. The pump cleaning cycle will run for as long as Clean Manual Input (29.088) remains set to On(1).

When set to Off(0), a manually started pump cleaning will stop wherever it is in the cleaning cycle. 

Clean Manual Input (29.088) is superseded if Hand or Auto mode is selected via Hand Select Input (29.013) and Auto Select Input (29.015).


See Cleaning Phase 1 Time At Reference (29.093) for a complete cleaning cycle profile diagram.


Parameter29.089  Clean On Start
Short descriptionWhen set to On, on start up, after pipe fill a cleaning cycle will run
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type1 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW

When set to On(1), this activates the pump cleaning cycle when the system is first run in Auto mode i.e. if the system goes to sleep and then wakes in Auto mode cleaning on start will not be triggered. If the pipe fill function is enabled via Pipe Fill Mode (29.075), then the pipe fill routine will happen first.

When set to Off(0), pump cleaning on start is disabled.

See Cleaning Phase 1 Time At Reference (29.093) for a complete cleaning cycle profile diagram.


Parameter29.090  Clean On Interval
Short descriptionWhen set to On, a clean cycle will be run at the user define interval
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type1 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW

When set to On, this activates cleaning on interval. The interval is started when Auto mode is selected where the pump cleaning cycle will happen at the end of the interval, each time the interval elapses. The interval is defined by Clean On Interval Time (29.096).

This method of cleaning is not available when Pump Control Mode (29.011) = Cascade.

See Cleaning Phase 1 Time At Reference (29.093) for a complete cleaning cycle profile diagram.


Parameter29.091  Clean On Load Current Threshold
Short descriptionWhen set to On, when the user defined load current is reached a cleaning cycle will run
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type1 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW

When set to On(1), this activates cleaning on current load thresholds defined by Clean On Load Current High Threshold (29.098) and Clean On Load Current Low Threshold (29.099). Intermittent cleaning load current conditions are filtered using the Clean On Load Current Delay (29.097). A high current can by caused by a blocked pump rotor, and low current can be caused by a blocked pump input. The low and high current threshold should be set outside of the normal pumping current range.

This method of cleaning is not available when Pump Control Mode (29.011) = Cascade.

See Cleaning Phase 1 Time At Reference (29.093) for a complete cleaning cycle profile diagram.


Parameter29.092  Clean On Motor Over-load
Short descriptionWhen set to On, if Pr10.017 = On then a cleaning cycle will be run
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type1 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW

When set to On(1), this activates cleaning on motor over-load as indicated when Motor Overload Alarm (10.017) = On(1). The Motor Thermal Time Constant 1 (04.015) must be set up correctly when using this feature; consult the pump motor manufacturer or documentation to find this value.

This method of cleaning is not available when Pump Control Mode (29.011) = Cascade.

See Cleaning Phase 1 Time At Reference (29.093) for a complete cleaning cycle profile diagram.


Parameter29.093  Cleaning Phase 1 Time At Reference
Short descriptionSets the cleaning phase 1 time at constant speed
ModeRFC‑A
Minimum0.1Maximum6553.5
Default15.0Unitss
Type16 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places1
CodingRW, BU

This defines the time in seconds that the pump will spend at Cleaning Phase 1 Reference (01.025) before moving to phase 2 of the pump cleaning cycle.


Parameter29.094  Cleaning Phase 2 Time At Reference
Short descriptionSets the cleaning phase 2 time at constant speed
ModeRFC‑A
Minimum0.1Maximum6553.5
Default10.0Unitss
Type16 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places1
CodingRW, BU

This defines the time in seconds that the pump will spend at Cleaning Phase 2 Reference (01.026) before moving to phase 3 of the pump cleaning cycle.

See Cleaning Phase 1 Time At Reference (29.093) for a complete cleaning cycle profile diagram.


Parameter29.095  Cleaning Phase 3 Time At Reference
Short descriptionSets the cleaning phase 3 time at constant speed
ModeRFC‑A
Minimum0.1Maximum6553.5
Default10.0Unitss
Type16 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places1
CodingRW, BU

This defines the time in seconds that the pump will spend at Cleaning Phase 3 Reference (01.027) before completing the pump cleaning cycle.

See Cleaning Phase 1 Time At Reference (29.093) for a complete cleaning cycle profile diagram.


Parameter29.096  Clean On Interval Time
Short descriptionSets the time interval in minutes between cleaning cycles
ModeRFC‑A
Minimum1Maximum65535
Default3600Unitsminutes
Type16 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, BU

This defines the pump cleaning time interval in minutes used when Clean On Interval (29.090) = On(1). If the drive is running in Auto mode, when Clean On Interval Time (29.096) elapses a cleaning cycle is actioned. If the drive is sleeping in Auto mode when the Clean On Interval Time (29.096) elapses, a clean will be actioned next time the drive runs.


Parameter29.097  Clean On Load Current Delay
Short descriptionSets the time delay before acting on detection of a high or low load current
ModeRFC‑A
Minimum0.1Maximum6553.5
Default10.0Unitss
Type16 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places1
CodingRW, BU

Clean On Load Current Delay (29.097) is only used when Clean On Load Current Threshold (29.091) = On(1).

This defines the continuous time in seconds that the motor load current must be below the Clean On Load Current Low Threshold (29.099) or above the Clean On Load Current High Threshold (29.098) to initiate a clean on load current. Clean On Load Current Delay (29.097) filters out any intermittent load current conditions that would otherwise trigger a clean on load current.

A high current can by caused by a blocked pump rotor, and low current can be caused by a blocked pump input. The low and high current threshold should be set outside of the normal pumping current range.


Parameter29.098  Clean On Load Current High Threshold
Short descriptionSets the high threshold for load current triggered cleaning
ModeRFC‑A
Minimum0.0Maximum200.0
Default80.0Units%
Type16 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places1
CodingRW, BU

Clean On Load Current High Threshold (29.098) is only used when Clean On Load Current Threshold (29.091) = On(1).

This defines the high load current threshold above which a clean on load current is initiated. Clean On Load Current High Threshold (29.098) is compared against Percentage Load (04.020). Clean On Load Current Delay (29.097) filters out any intermittent load current conditions that would otherwise trigger a clean on load current.

A high current can by caused by a blocked pump rotor, and low current can be caused by a blocked pump input. The low and high current threshold should be set outside of the normal pumping current range.


Parameter29.099  Clean On Load Current Low Threshold
Short descriptionSets the low threshold for load current triggered cleaning
ModeRFC‑A
Minimum0.0Maximum50.0
Default10.0Units%
Type16 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places1
CodingRW, BU

Clean On Load Current Low Threshold (29.099) is only used when Clean On Load Current Threshold (29.091) = On(1).

This defines the low load current threshold below which a clean on load current is initiated. Clean On Load Current Low Threshold (29.099) is compared against Percentage Load (04.020). Clean On Load Current Delay (29.097) filters out any intermittent load current conditions that would otherwise trigger a clean on load current.

A high current can by caused by a blocked pump rotor, and low current can be caused by a blocked pump input. The low and high current threshold should be set outside of the normal pumping current range.


Parameter29.100  Clean Per Hour Limit
Short descriptionSets the maximum number of cleaning cycles per hour
ModeRFC‑A
Minimum1Maximum30
Default5Units 
Type8 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, BU

This defines the maximum number of pump cleaning cycles per hour. The action taken when the limit is reached is configured by the Clean Per Hour Limit Mode (29.101). When this limit is reached the Clean Per Hour Alarm Output (29.105) = On(1).


Parameter29.101  Clean Per Hour Limit Mode
Short descriptionSets the clean per hour limit mode
ModeRFC‑A
Minimum0Maximum2
Default1Units 
Type8 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, TE, BU

ValueTextDescription
0Alarm OnlyAn alarm will be raised but cleaning will continue
1Stop CleaningAn alarm will be raised and cleaning is stopped for 1hour
2TripThe drive will trip

This sets the action taken when the Clean Per Hour Limit (29.100) is reached. The following modes are available:

Mode Value Description
Alarm Only 0 An alarm will be raised where Clean Per Hour Alarm Output (29.105) is set to On(1) when the limit is reached.
Stop Cleaning 1 An alarm will be raised where Clean Per Hour Alarm Output (29.105) is set to On(1) and cleaning will be deactivated for the remainder of the current hour when the limit is reached.
Trip 2 The drive will trip Clean Over-cycle when the clean per hour limit is reached. Resetting the trip will reset the internal clean per hour counters so that cleaning can continue after the reset if triggered.


 


Parameter29.102  Pre-clean Load Current
Short descriptionIndicate the pre-clean load current percentage
ModeRFC‑A
Minimum-1000.0Maximum1000.0
Default0.0Units%
Type32 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places1
CodingRW, PR, NC

This indicates the load current percentage sampled from Percentage Load (04.020) prior to running the cleaning cycle. By using Pre-clean Load Current (29.102) and comparing it to Post-clean Load Current (29.103) it is possible to see if the cleaning cycle was effective.

Pre-clean Load Current (29.102) and Post-clean Load Current (29.103) are not updated if the cleaning cycle was started either manually via Clean Manual Input (29.088) or on start up via Clean On Start (29.089).   


Parameter29.103  Post-clean Load Current
Short descriptionIndicate the post-clean load current percentage
ModeRFC‑A
Minimum-1000.0Maximum1000.0
Default0.0Units%
Type32 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places1
CodingRW, PR, NC

This indicates the load current percentage sampled from Percentage Load (04.020) after running the cleaning cycle. By using Pre-clean Load Current (29.102) and comparing it to Post-clean Load Current (29.103) it is possible to see if the cleaning cycle was effective.


Parameter29.104  Clean Active Output
Short descriptionIndicates when a cleaning cycle is running
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type8 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, PR, TE, NC, BU

ValueText
0Off
1On

This indicates when a pump cleaning cycle is running.


Parameter29.105  Clean Per Hour Alarm Output
Short descriptionIndicates when the clean per hour limit has been reached
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type8 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, PR, TE, NC, BU

ValueText
0Off
1On

When Clean Per Hour Limit Mode (29.101) = Alarm Only or Stop Cleaning, this indicates when the Clean Per Hour Limit (29.100) has been reached.


Parameter29.106  Assist Control Mode
Short descriptionSets the I/O control mode for assist soft starters in a Cascade system
ModeRFC‑A
Minimum0Maximum2
Default0Units 
Type8 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, TE, BU

ValueTextDescription
0Run OnlyThe assist starter will be controlled using a run output only
1Full I/OThe assist starters will be controlled using Run output, Ready Input and Running Input.
2Run+ReadyThe assist starters will be controlled using Run output and Ready Input.

Assist Control Mode (29.106) is only used when Pump Control Mode (29.011) = Cascade or Cascade Leader.

This selects how much I/O is required to control assist soft starters. Three options are available:

Mode Value Description
Run Only 0

In this mode assist Soft Starters are only provided a run command signal via Assist 1 Run Output (29.107), Assist 2 Run Output (29.113) Assist 3 Run Output and Assist 4 Run Output. The assist run outputs  must be routed to digital outputs that are connected to Soft Starter run inputs. 

It is assumed that a Soft Starter is running after the Add Assist Delay (29.122) has elapsed. If the Soft Starter pump has contributed enough, the main process PID output will reduce and no further Soft Starters will be commanded to run. If the Soft Starter pump hasn’t contributed enough, the main process PID output will remain high and another Soft Starter will be commanded to run.

The number of pumps that are physically in the system are set using Number Of Pumps (29.171), e.g. in a system with 1 F600 and 3 assist Soft Starters Number Of Pumps (29.171) is set to 4. 

Full I/O 1

In this mode assist soft starter controlled and monitored using the following control and status signals:
• Assist 1 Run Output (29.107) and Assist 2 Run Output (29.113).
• Assist 1 Ready Input (29.108) and Assist 2 Ready Input (29.114).
• Assist 1 Running Input (29.109) and Assist 2 Running Input (29.115).

If the Soft Starter pump has contributed enough, the main process PID output will reduce and no further Soft Starters will be commanded to run. If the Soft Starter pump hasn’t contributed enough, the main process PID output will remain high and another Soft Starter will be commanded to run.


The Ready input is used to determine whether to attempt to start a given Soft Starter. If the Soft Starter indicates that it is “Ready” then it will be started if required. If it does not indicate that it is “Ready” then an alternative Soft Starter will be started instead if available. If a Soft Starter does not give a Ready signal during pumping, its run output will be set to off and it will not be retried until it gives a Ready signal again. If a Soft Started does not give a running signal withinAdd Assist Delay (29.122) the the Run output for that Soft Starter will be set to Off, and an alternative Soft Starter will be started instead if available.


The Running input is used to give a more accurate running time for a given starter, and to provide indication on whether the start was successful or not via Assist Last Failed Start (29.119).

The number of pumps that are physically in the system are set using Number Of Pumps (29.171), e.g. in a system with 1 F600 and 3 assist Soft Starters Number Of Pumps (29.171) is set to 4. 

Run+Ready 2

In this mode assist soft starter controlled and monitored using the following control and status signals:
• Assist 1 Run Output (29.107) and Assist 2 Run Output (29.113).
• Assist 1 Ready Input (29.108) and Assist 2 Ready Input (29.114).

If the Soft Starter pump has contributed enough, the main process PID output will reduce and no further Soft Starters will be commanded to run. If the Soft Starter pump hasn’t contributed enough, the main process PID output will remain high and another Soft Starter will be commanded to run.

The Ready input is used to determine whether to attempt to start a given Soft Starter. If the Soft Starter indicates that it is “Ready” then it will be started if required. If it does not indicate that it is “Ready” then an alternative Soft Starter will be started instead, if one available. If a Soft Starter does not give a Ready signal during pumping, its run output will be set to off and it will not be retried until it gives a Ready signal again.

The number of pumps that are physically in the system are set using Number Of Pumps (29.171), e.g. in a system with 1 F600 and 3 assist Soft Starters Number Of Pumps (29.171) is set to 4.

The Soft Starter assists are called to run or stop using Add Assist Delay (29.122), Add Assist Band (29.123) and Remove Assist Delay (29.124). The starting order of the Soft Starter assists is rotated using the Alternation Time (29.125).

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.

When Pump Control Mode (29.011) = Cascade Leader and Assist Control Mode (29.106) = Full I/O OR Run+Ready, and there are no pumps “Ready” as indicated by Assist 1 Ready Input (29.108), Assist 2 Ready Input (29.114), Assist 3 Ready Input (29.160), and Assist 4 Ready Input (29.166) are all set to Off(0), the drive will wait in this state until a pump becomes “Ready”.


Parameter29.107  Assist 1 Run Output
Short descriptionOff = Stop, On = Run.
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type8 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, PR, TE, NC, BU

ValueText
0Off
1On

This is the Run command output for Assist 1. A digital output must be routed to this parameter where the subsequent 24V signal is connected to the run Input of Soft Starter Assist 1.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.108  Assist 1 Ready Input
Short descriptionOff = Not ready, On = Ready.
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type8 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, TE, NC, BU

ValueText
0Off
1On

Assist 1 Ready Input (29.108) is only used when Assist Control Mode (29.106) = Full I/O or Run+Ready.

This is the Ready feedback input for Assist 1. A digital input must be routed to this parameter where a 24V signal is connected to a ready or healthy output from Soft Starter Assist 1.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.109  Assist 1 Running Input
Short descriptionOff = Not Running, On = Running.
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type8 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, TE, NC, BU

ValueText
0Off
1On

Assist 1 Running Input (29.109) is only used when Assist Control Mode (29.106) = Full I/O.

This is the Running feedback input for Assist 1. A digital input must be routed to this parameter where a 24V signal is connected to a running output from Soft Starter Assist 1.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.110  Assist 1 Runtime
Short descriptionAssist 1 run time since power up in minutes
ModeRFC‑A
Minimum0Maximum2147483647
Default0Unitsminutes
Type32 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, PR, NC

This indicates the running time for Assist Soft Starter 1 in minutes since the Leader drive was powered up.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.111  Assist 1 Lockout Countdown
Short descriptionIndicates the time remaining until assist 1 can be restarted
ModeRFC‑A
Minimum0.0Maximum3600.0
Default0.0Unitss
Type16 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places1
CodingRW, PR, NC, BU

In the event that Assist Starts Per Hour (29.120) has been reached by Assist Soft Starter 1, Assist 1 Lockout Countdown (29.111) indicates the remaining time in seconds that this Soft Starter is locked out for to allow time for it to cool down.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.112  Assist 1 Lockout Output
Short descriptionIndicates when Assist 1 has been locked out due to too many starts per hour
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type8 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, PR, TE, NC, BU

ValueText
0Off
1On

In the event that Assist Starts Per Hour (29.120) has been reached by Assist Soft Starter 1, Assist 1 Lockout Output (29.112) indicates when this Soft Starter is locked out to allow time for it to cool down.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.113  Assist 2 Run Output
Short descriptionOff = Stop, On = Run.
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type8 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, PR, TE, NC, BU

ValueText
0Off
1On

This is the Run command output for Assist 2. A digital output must be routed to this parameter where the subsequent 24V signal is connected to the run Input of Soft Starter Assist 2.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.114  Assist 2 Ready Input
Short descriptionOff = Not ready, On = Ready.
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type8 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, TE, NC

ValueText
0Off
1On

Assist 2 Ready Input (29.114) is only used when Assist Control Mode (29.106) = Full I/O.

This is the Ready feedback input for Assist 2. A digital input must be routed to this parameter where a 24V signal is connected to a ready or healthy output from Soft Starter Assist 2.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.115  Assist 2 Running Input
Short descriptionOff = Not Running, On = Running.
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type8 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, TE, NC

ValueText
0Off
1On

Assist 2 Running Input (29.115) is only used when Assist Control Mode (29.106) = Full I/O.

This is the Running feedback input for Assist 2. A digital input must be routed to this parameter where a 24V signal is connected to a running output from Soft Starter Assist 2.


Parameter29.116  Assist 2 Runtime
Short descriptionAssist 2 run time since power up in minutes
ModeRFC‑A
Minimum0Maximum2147483647
Default0Unitsminutes
Type32 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, PR, NC

This indicates the running time for Assist Soft Starter 2 in minutes since the Leader drive was powered up.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.117  Assist 2 Lockout Countdown
Short descriptionIndicates the time remaining until assist 2 can be restarted
ModeRFC‑A
Minimum0.0Maximum3600.0
Default0.0Unitss
Type16 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places1
CodingRW, PR, NC, BU

In the event that Assist Starts Per Hour (29.120) has been reached by Assist Soft Starter 2, Assist 2 Lockout Countdown (29.117) indicates the remaining time in seconds that this Soft Starter is locked out for to allow time for it to cool down.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.118  Assist 2 Lockout Output
Short descriptionIndicates when Assist 2 has been locked out due to too many starts per hour
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type8 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, PR, TE, NC, BU

ValueText
0Off
1On

In the event that Assist Starts Per Hour (29.120) has been reached by Assist Soft Starter 2, Assist 2 Lockout Output (29.118) indicates when this Soft Starter is locked out to allow time for it to cool down.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.119  Assist Last Failed Start
Short descriptionIndicates which assist failed to start last
ModeRFC‑A
Minimum0Maximum2
Default0Units 
Type8 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, TE, BU

ValueText
0No Failed Starts
1Assist 1 Fail
2Assist 2 Fail

When Assist Control Mode (29.106) = Full I/O, Assist Last Failed Start (29.119) indicates which starter failed to run as indicated by Assist 1 Running Input (29.109), Assist 2 Running Input (29.115), Assist 3 Running Input (29.161) or Assist 4 Running Input (29.167) failing to change to On(1) within the Add Assist Delay (29.122) + 1 second.

When Assist Control Mode (29.106) = Run Only, Assist Last Failed Start (29.119) is set to No Failed Starts.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.120  Assist Starts Per Hour
Short descriptionThe number of times a soft starter assist can be started in 1 hour
ModeRFC‑A
Minimum1Maximum60
Default5Units 
Type8 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, BU

This defines the maximum number of starts per hour for Soft Starter Assist 1 to 4. Please consult the Soft Starter documentation to find out how many starts per hour the particular Soft Starter used in the system is rated for.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.121  Assist Over-cycle Mode
Short descriptionSets what will happen when the starts per hour limit is reached
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type8 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, TE, BU

ValueTextDescription
0Wait 1hr CoolWait 1 hour to cool down then permit restart
1TripTrip when the limit is reached

This defines how the assist over-cycle detection will be handled by the Leader drive. Assist over-cycle is always enabled to protect the Soft Starter. The following options are available:

Mode Value Description
Wait 1hr Cool 0 In this mode the system will wait 1 hour from the last permitted start for the Soft Starter to cool down. After the cooling time has elapsed the Soft Starter will be allowed to run again automatically.
Trip 1 In this mode the drive will trip Assist 1 Cycle, Assist 2 Cycle, Assist 3 Cycle or Assist 4 Cycle indicating an over-cycle, and the system will wait 1 hour from the last permitted start for the Soft Starter to cool down. After the cooling time has elapsed and the trip is cleared the Soft Starter will be allowed to run again automatically. By default, the system will auto-reset the trip, but the Soft Starter over-cycle trip will be logged in the drives trip log (Trip 0 (10.020) to Trip 9 (10.029)) for diagnostic purposes.

The Over-cycle Starts Per Hour (29.128) used to detect an assist over-cycle condition.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.122  Add Assist Delay
Short descriptionA time filter applied to the add assist conditions
ModeRFC‑A
Minimum0.0Maximum6553.5
Default3.0Unitss
Type16 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places1
CodingRW, BU

Add Assist Delay (29.122) is used when Pump Control Mode (29.011) = Cascade or Multi-leader.

This defines the continuous time period in seconds that the leader drive main process PID must set the drive output frequency or speed within the Add Assist Band (29.123) until an assist drive or soft starter is requested. Add Assist Delay (29.122) is used to filter intermittent entry to the Add Assist Band (29.123).

In a Cascade or Multi-leader system the Wake Detect Feedback Threshold (29.049) is used in combination with the Add Assist Band (29.123) to decide when to start an assist i.e. both the add assist and wake thresholds must be satisfied to start an assist.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.123  Add Assist Band
Short descriptionThe band below the maximum frequency / speed whare an assist drive or soft starter will be requested
ModeRFC‑A
Minimum0.0Maximum3000.0
Default30.0Units 
Type32 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places1
CodingRW

Add Assist Band (29.123) is used when Pump Control Mode (29.011) = Cascade or Multi-leader.

This defines the frequency or speed band in which an assist Drive or Soft Starter will be requested by the Leader Drive, after the Add Assist Delay (29.122) has elapsed. The top end of this band is aligned with the Maximum Reference Clamp (01.006) i.e. the add assist band moves with the maximum reference clamp.

In a Cascade or Multi-leader system the Wake Detect Feedback Threshold (29.049) is used in combination with the Add Assist Band (29.123) to decide when to start an assist i.e. both the add assist and wake thresholds must be satisfied to start an assist.

This is used in both Cascade and Multi-leader systems to add an assist soft starter or drive.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.124  Remove Assist Delay
Short descriptionA time filter applied to the remove assist conditions
ModeRFC‑A
Minimum0.0Maximum6553.5
Default3.0Unitss
Type16 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places1
CodingRW, BU

Remove Assist Delay (29.124) is used when Pump Control Mode (29.011) = Cascade or Multi-leader.

This defines the continuous time period in seconds that the leader drive main process PID must set the drive output frequency or speed below the Sleep Detect Speed Threshold (29.051) until an assist drive or soft starter is stopped, (Sleeping). Remove Assist Delay (29.124) is used to filter intermittent entry to the Sleep Detect Speed Threshold (29.051).

This is used in both Cascade and Multi-leader systems to add an assist soft starter or drive.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


 


Parameter29.125  Alternation Time
Short descriptionThe time in a cascade or multi-leader system to rotate the starting order
ModeRFC‑A
Minimum0.0Maximum3276.7
Default24.0Unitshours
Type16 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places1
CodingRW

In a Cascade system, (Pump Control Mode (29.011) = Cascade), this defines the time period in hours that the a given assist starting order will be used for. When the time elapses the starting sequence of the Assists will be swapped. The starting sequences are:

In a Multi-leader system, (Pump Control Mode (29.011) = Multi-leader),this defines the time period in hours that in that an individual drive will be the system Leader. When the time elapses, the Leader will be passed to the next drive in the sequence. The drive starting sequences are 1- 2-3, 2-3-1, 3-1-2.

The number of pumps that are physically in the system are set using Number Of Pumps (29.171), e.g. in a system with 1 F600 and 3 assist Soft Starters Number Of Pumps (29.171) is set to 4. This affects the starting order pattern e.g. if Number Of Pumps (29.171) = 4 in a Cascade system, assist 4 is not included in the alternation pattern.

Setting Alternation Time (29.125) to 0 prevents the system from automatically alternating the assist order in a cascade system, or the leader drive and assists in a multi-leader system.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.

In a Cascade Leader system, (Pump Control Mode (29.011) = Cascade Leader), this defines the time period in hours that the a given assist starting order will be used for. When the time elapses the starting sequence of the Assists will be swapped. The starting sequences are:


Parameter29.126  Alternation Time Elapsed
Short descriptionThe elapsed time in a cascade or multi-leader system with the current starting order
ModeRFC‑A
Minimum0.0Maximum3276.7
Default0.0Unitshours
Type16 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places1
CodingRW, PR, NC

Alternation Time Elapsed (29.126) is used when Pump Control Mode (29.011) = Cascade, Multi-leader or Cascade Leader.

This indicates the the alternation time elapsed so far in hours. When Alternation Time Elapsed (29.126) = Alternation Time (29.125) the system will alternate the running order of the connected Drives or Soft Starters. See Alternation Time (29.125).

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.127  Over-cycle Mode
Short descriptionSets what the system will do when the over-cycle starts per hour limit is reached
ModeRFC‑A
Minimum0Maximum3
Default1Units 
Type8 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, TE, BU

ValueTextDescription
0DisabledThe over-cycle threshold is disabled
1Alarm OnlyWhen the over-cycle threshold is reached indicate an alarm only
2TripWhen the over-cycle threshold is reached trip
3Inc SetpointWhen the over-cycle threshold is reached indicate an alarm and increase the setpoint

This defines the over-cycle protection mode used by a single drive application like Single Pump, and when the drive is a Leader in a Cascade or Multi-Leader system. Soft Starter Assist over-cycle is always enabled and is handled separately; See Assist Starts Per Hour (29.120) and Assist Over-cycle Mode (29.121).

The following over-cycle modes are available:

Mode Value Description
Disabled 0 Over-cycle protection is disabled.
Alarm Only 1 When the Over-cycle Starts Per Hour (29.128) has been reached the system will indicate an alarm via the Over-cycle Alarm Output (29.131)
Trip 2 When the Over-cycle Starts Per Hour (29.128) has been reached the system will trip Over-cycle.
Inc Setpoint 3 When the Over-cycle Starts Per Hour (29.128) has been reached the system will indicate an alarm via the Over-cycle Alarm Output (29.131) and the PID setpoint will be increased by the Over-cycle Setpoint Increment (29.129) in order to keep the system running. The maximum amount that the PID setpoint can be increased by is set by Over-cycle Setpoint Increment Maximum (29.130). An alarm is given via the Over-cycle Alarm Output (29.131) when Over-cycle Setpoint Increment Maximum (29.130) is reached.
This helps prevent the system from going to sleep as often thereby reducing the number of starts per hour. An alternative to this is to use PID1 Pre-sleep Boost Level (14.028) and PID1 Pre-Sleep Maximum Boost Time  (14.029).

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.128  Over-cycle Starts Per Hour
Short descriptionSets the maximum number of starts per hour threshold for the over-cycle protection
ModeRFC‑A
Minimum0Maximum255
Default5Units 
Type8 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, BU

Sets the maximum number of starts per hour threshold for the over-cycle detection system. The internal count of starts is reset every hour. See Over-cycle Mode (29.127) for more details.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.129  Over-cycle Setpoint Increment
Short descriptionSets the amount to increase the setpoint by in the event of over-cycling
ModeRFC‑A
Minimum0.01Maximum2.00
Default0.01Units%
Type16 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places2
CodingRW, BU

Over-cycle Setpoint Increment (29.129) is only used when Over-cycle Mode (29.127) = Inc Setpoint.

This defines the amount that will be added to the main process PID setpoint in the event that an over-cycle condition is detected. The maximum amount that the main process PID setpoint can be increased by is defined by Over-cycle Setpoint Increment Maximum (29.130). This helps prevent the system from going to sleep as often thereby reducing the number of starts per hour. 

See Over-cycle Mode (29.127) for more details.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.130  Over-cycle Setpoint Increment Maximum
Short descriptionThis defines the maximum amount that will be added to the PID setpoint when it is incremented.
ModeRFC‑A
Minimum0.01Maximum15.00
Default0.60Units%
Type16 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places2
CodingRW, BU

Over-cycle Setpoint Increment Maximum (29.130) is only used when Over-cycle Mode (29.127) = Inc Setpoint.

This defines the maximum amount that will be added to the main process PID setpoint in the event that an over-cycle condition is detected. The ammount that the main process PID setpoint is increased by is defined by Over-cycle Setpoint Increment (29.129). This helps prevent the system from going to sleep as often thereby reducing the number of starts per hour. 

See Over-cycle Mode (29.127) for more details.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.131  Over-cycle Alarm Output
Short descriptionIndicates when the over-cycle limit has been reached
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type8 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, PR, TE, NC, BU

ValueText
0Off
1On

In the event that Over-cycle Starts Per Hour (29.128) has been reached Over-cycle Alarm Output (29.131) is set to On(1).

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.132  Multi-leader Node ID
Short descriptionThe node ID for this drive in a multi-leader system
ModeRFC‑A
Minimum1Maximum3
Default1Units 
Type8 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, BU

Multi-leader Node ID (29.132) is only used when Pump Control Mode (29.011) = Multi-leader.

This defines the node ID of this drive within a Multi-leader pump system. The number must be either 1,2 or 3. Note that if only 2 drives exist in the system then 1 or 2 should be selected. This tells the system software how to configure the Ethernet communications used to pass control and status data between the drives and is used by the Multi-leader control and scheduling.

The drive assists are called to run or stop using Add Assist Delay (29.122), Add Assist Band (29.123) and Remove Assist Delay (29.124). The starting order of the Leader and drive assists is rotated using the Alternation Time (29.125).

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.133  Multi-leader Network Loss Mode
Short descriptionMulti-leader system Node 1 status word
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type8 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, TE, BU

ValueText
0Run Single Pump
1Trip

Multi-leader Node ID (29.132) is only used when Pump Control Mode (29.011) = Multi-leader.

This defines how the pump drive will respond in the event that Ethernet communications are lost to the Leader while running in Auto mode.

When set to Run Single Pump, the system will switch internally to run as a Single Pump, (Pump Control Mode (29.011) = Single Pump).

When set to Trip, the system will trip Network Loss if the connection is lost to the Leader drive.


Parameter29.134  Multi-leader Node 1 Status Word
Short descriptionMulti-leader system Node 1 status word
ModeRFC‑A
Minimum0
(Display: 0000000000000000)
Maximum65535
(Display: 1111111111111111)
Default0
(Display: 0000000000000000)
Units 
Type16 Bit VolatileUpdate RateBackground
Display FormatBinaryDecimal Places0
CodingRW, PR, NC, BU

This parameter is only used when Pump Control Mode (29.011) = Multi-leader.

Multi-leader Node 1 Status Word (29.134) is used by the pump software as part of a Multi-leader system for drive node 1. The user is not intended to modify this value.

The following status bits are available:

Status Bit Description
0 Drive On Network
1 Ready
2 Auto running
3 Drive Active
4 Loss Of Feedback
5 Hand Selected
6 Auto Selected
7 Pipe Fill Complete
8 Clean Request
9 Clean Permit

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.135  Multi-leader Node 1 PID Output
Short descriptionMulti-leader system Node 1 PID output percentage
ModeRFC‑A
Minimum-3276.8Maximum3276.7
Default0.0Units 
Type32 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places1
CodingRW, PR, NC

This parameter is only used when Pump Control Mode (29.011) = Multi-leader.

Multi-leader Node 1 PID Output (29.135) is used by the pump software as part of a Multi-leader system for drive node 1. The user is not intended to modify this value.

This indicates the main process PID output represented as a frequency or speed.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.136  Multi-leader Node 1 Control Word
Short descriptionMulti-leader system Node 1 control word
ModeRFC‑A
Minimum0
(Display: 0000000000000000)
Maximum65535
(Display: 1111111111111111)
Default0
(Display: 0000000000000000)
Units 
Type16 Bit VolatileUpdate RateBackground
Display FormatBinaryDecimal Places0
CodingRW, PR, NC, BU

This parameter is only used when Pump Control Mode (29.011) = Multi-leader.

Multi-leader Node 1 Control Word (29.136) is used by the pump software as part of a Multi-leader system  for drive node 1. The user is not intended to modify this value.

The following control bits are available:

Control Bit Description
0 Run drive node 1
1 Run drive node 2
2 Run drive node 3

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.137  Multi-leader Node 1 Lead Drive
Short descriptionIndicates which node is the system is the leader
ModeRFC‑A
Minimum0Maximum3
Default0Units 
Type8 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, PR, NC, BU

This parameter is only used when Pump Control Mode (29.011) = Multi-leader.

Multi-leader Node 1 Lead Drive (29.137) is used by the pump software as part of a Multi-leader system  for drive node 1. The user is not intended to modify this value.

This indicates the current system leader, and is used change the Leader drive over after the Alternation Time (29.125) has elapsed.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.138  Multi-leader Node 1 PID Feedback
Short descriptionMulti-leader system Node 1 PID feedback percentage
ModeRFC‑A
Minimum-327.68Maximum327.67
Default0.00Units%
Type16 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places2
CodingRW, PR, NC

This parameter is only used when Pump Control Mode (29.011) = Multi-leader.

Multi-leader Node 1 PID Feedback (29.138) is used by the pump software as part of a Multi-leader system for drive node 1. The user is not intended to modify this value.

This indicates the the main process PID feedback after the filter has been applied, PID Final Feedback Percent (29.035). This is used by other drive nodes if the local PID feedback is not working.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.139  Multi-leader Node 2 Status Word
Short descriptionMulti-leader system Node 2 status word
ModeRFC‑A
Minimum0
(Display: 0000000000000000)
Maximum65535
(Display: 1111111111111111)
Default0
(Display: 0000000000000000)
Units 
Type16 Bit VolatileUpdate RateBackground
Display FormatBinaryDecimal Places0
CodingRW, PR, NC, BU

This parameter is only used when Pump Control Mode (29.011) = Multi-leader.

Multi-leader Node 2 Status Word (29.139) is used by the pump software as part of a Multi-leader system for drive node 2. The user is not intended to modify this value.

The following status bits are available:

Status Bit Description
0 Drive On Network
1 Ready
2 Auto running
3 Drive Active
4 Loss Of Feedback
5 Hand Selected
6 Auto Selected
7 Pipe Fill Complete
8 Clean Request
9 Clean Permit

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.140  Multi-leader Node 2 PID Output
Short descriptionMulti-leader system Node 2 PID output percentage
ModeRFC‑A
Minimum-3276.8Maximum3276.7
Default0.0Units 
Type32 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places1
CodingRW, PR, NC

This parameter is only used when Pump Control Mode (29.011) = Multi-leader.

Multi-leader Node 2 PID Output (29.140) is used by the pump software as part of a Multi-leader system for drive node 2. The user is not intended to modify this value..

This indicates the main process PID output represented as a frequency or speed.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.141  Multi-leader Node 2 Control Word
Short descriptionMulti-leader system Node 2 control word
ModeRFC‑A
Minimum0
(Display: 0000000000000000)
Maximum65535
(Display: 1111111111111111)
Default0
(Display: 0000000000000000)
Units 
Type16 Bit VolatileUpdate RateBackground
Display FormatBinaryDecimal Places0
CodingRW, PR, NC, BU

This parameter is only used when Pump Control Mode (29.011) = Multi-leader.

Multi-leader Node 2 Control Word (29.141) is used by the pump software as part of a Multi-leader system  for drive node 2. The user is not intended to modify this value

The following control bits are available:

Control Bit Description
0 Run drive node 1
1 Run drive node 2
2 Run drive node 3

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.142  Multi-leader Node 2 Lead Drive
Short descriptionIndicates which node is the system is the leader
ModeRFC‑A
Minimum0Maximum3
Default0Units 
Type8 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, PR, NC, BU

This parameter is only used when Pump Control Mode (29.011) = Multi-leader.

Multi-leader Node 2 Lead Drive (29.142) is used by the pump software as part of a Multi-leader system  for drive node 2. The user is not intended to modify this value. .

This indicates the current system leader, and is used change the Leader drive over after the Alternation Time (29.125) has elapsed.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.143  Multi-leader Node 2 PID Feedback
Short descriptionMulti-leader system Node 2 PID feedback percentage
ModeRFC‑A
Minimum-327.68Maximum327.67
Default0.00Units%
Type16 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places2
CodingRW, PR, NC

This parameter is only used when Pump Control Mode (29.011) = Multi-leader.

Multi-leader Node 2 PID Feedback (29.143) is used by the pump software as part of a Multi-leader system for drive node 2. The user is not intended to modify this value.

This indicates the the main process PID feedback after the filter has been applied, PID Final Feedback Percent (29.035). This is used by other drive nodes if the local PID feedback is not working.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.144  Multi-leader Node 3 Status Word
Short descriptionMulti-leader system Node 3 status word
ModeRFC‑A
Minimum0
(Display: 0000000000000000)
Maximum65535
(Display: 1111111111111111)
Default0
(Display: 0000000000000000)
Units 
Type16 Bit VolatileUpdate RateBackground
Display FormatBinaryDecimal Places0
CodingRW, PR, NC, BU

This parameter is only used when Pump Control Mode (29.011) = Multi-leader.

Multi-leader Node 3 Status Word is used by the pump software as part of a Multi-leader system for drive node 3. The user is not intended to modify this value.

The following status bits are available:

Status Bit Description
0 Drive On Network
1 Ready
2 Auto running
3 Drive Active
4 Loss Of Feedback
5 Hand Selected
6 Auto Selected
7 Pipe Fill Complete
8 Clean Request
9 Clean Permit


Parameter29.145  Multi-leader Node 3 PID Output
Short descriptionMulti-leader system Node 3 PID output percentage
ModeRFC‑A
Minimum-3276.8Maximum3276.7
Default0.0Units 
Type32 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places1
CodingRW, PR, NC

This parameter is only used when Pump Control Mode (29.011) = Multi-leader.

Multi-leader Node 3 PID Output (29.145) is used by the pump software as part of a Multi-leader system for drive node 3. The user is not intended to modify this value.

This indicates the main process PID output represented as a frequency or speed.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.146  Multi-leader Node 3 Control Word
Short descriptionMulti-leader system Node 3 control word
ModeRFC‑A
Minimum0
(Display: 0000000000000000)
Maximum65535
(Display: 1111111111111111)
Default0
(Display: 0000000000000000)
Units 
Type16 Bit VolatileUpdate RateBackground
Display FormatBinaryDecimal Places0
CodingRW, PR, NC, BU

This parameter is only used when Pump Control Mode (29.011) = Multi-leader.

Multi-leader Node 3 Control Word (29.146) is used by the pump software as part of a Multi-leader system  for drive node 3. The user is not intended to modify this value.  

The following control bits are available:

Control Bit Description
0 Run drive node 1
1 Run drive node 2
2 Run drive node 3

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.147  Multi-leader Node 3 Lead Drive
Short descriptionIndicates which node is the system is the leader
ModeRFC‑A
Minimum0Maximum3
Default0Units 
Type8 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, PR, NC, BU

This parameter is only used when Pump Control Mode (29.011) = Multi-leader.

Multi-leader Node 3 Lead Drive (29.147) is used by the pump software as part of a Multi-leader system  for drive node 3. The user is not intended to modify this value.

This indicates the current system leader, and is used change the Leader drive over after the Alternation Time (29.125) has elapsed.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.148  Multi-leader Node 3 PID Feedback
Short descriptionMulti-leader system Node 3 PID feedback percentage
ModeRFC‑A
Minimum-327.68Maximum327.67
Default0.00Units%
Type16 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places2
CodingRW, PR, NC

This parameter is only used when Pump Control Mode (29.011) = Multi-leader.

Multi-leader Node 3 PID Feedback (29.148) is used by the pump software as part of a Multi-leader system for drive node 3. The user is not intended to modify this value.

This indicates the the main process PID feedback after the filter has been applied, PID Final Feedback Percent (29.035). This is used by other drive nodes if the local PID feedback is not working.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.150  Pump Control Word Watchdog Time
Short descriptionSets the pump control word watchdog trip time in seconds
ModeRFC‑A
Minimum0.0Maximum60.0
Default2.0Unitss
Type16 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places1
CodingRW, BU

This is only used if Control Input Mode (29.012) = Ctrl Wrd or Ctrl Wrd & Input where the control word is enabled.

When set to 0, the control word watchdog feature is disabled.

When set >0, the watchdog feature is enabled where Pump Control Word 1 (29.151) watchdog bit must be toggled 1 to 0 or 0 to 1 inside this time period otherwise a Ctrl Wrd Watchdg trip will occur stopping the system. The watchdog is only started after the first time a change in state of the watchdog bit, Pump Control Word 1 (29.151) bit 15, is seen.

On power up there is a delay of 30s before the watchdog is assessed to allow a commanding HMI or PLC to start up.


Parameter29.151  Pump Control Word 1
Short descriptionPump software control word 1
ModeRFC‑A
Minimum0
(Display: 0000000000000000)
Maximum65535
(Display: 1111111111111111)
Default0
(Display: 0000000000000000)
Units 
Type16 Bit VolatileUpdate RateBackground
Display FormatBinaryDecimal Places0
CodingRW, NC, BU

This is remote control word 1, intended to be used by a HMI or PLC to control the Pump drive when Control Input Mode (29.012) = Ctrl Wrd or Ctrl Wrd & Input.
The following control bits are available:

Bit Functionality
0 Remote software enable and disable via Drive Enable (06.015). 0 = disable the drive, 1 = enable the drive. This is in addition to the drives STO input; this is not a safety input. 
1 Drive reset via Drive Reset (10.033).
2 Hand select input, similar to Hand Select Input (29.013).
3 Reserved
4 Auto select input, similar to Auto Select Input (29.015).
5 Reset volume input, similar to Reset Volume Input (29.010).
6 PID setpoint select input 0, similar to PID Setpoint Select Input 0 (29.026).
7 PID setpoint select input 1, similar to PID Setpoint Select Input 1 (29.027).
8 Timer schedule run input, similar to Time Schedule Run Input (29.056).
9 Flow switch input, similar to Flow Switch Input (29.066). Note that if a flow switch is not connected that this must be set to 1 to disbale the no flow switch input functionality.
10 Level switch high input, similar to Level Switch High Input (29.079).
11 Level switch low input, similar to Level Switch Low Input (29.080).
12 External pump fault input, similar to External Pump Fault Input (29.085).
13 Motor thermal protection input, similar to Motor Thermal Protection Input (29.086)
14 Pump cleaning manual input, similar to Clean Manual Input (29.088).
15 Watchog input from a HMI or PLC. See Pump Control Word Watchdog Time (29.150).


Parameter29.152  Pump Control Word 2
Short descriptionPump software control word 2
ModeRFC‑A
Minimum0
(Display: 0000000000000000)
Maximum65535
(Display: 1111111111111111)
Default0
(Display: 0000000000000000)
Units 
Type16 Bit VolatileUpdate RateBackground
Display FormatBinaryDecimal Places0
CodingRW, NC, BU

This is remote control word 2, intended to be used by a HMI or PLC to control the Pump drive when Control Input Mode (29.012) = Ctrl Wrd or Ctrl Wrd & Input.
The following control bits are available:

Bit Functionality
0 Assist 1 ready input, similar to Assist 1 Ready Input (29.108).
1 Assist 1 running input, similar to Assist 1 Running Input (29.109).
2 Assist 2 ready input, similar to Assist 2 Ready Input (29.114).
3 Assist 2 running input, similar to Assist 2 Running Input (29.115).
4 Assist 3 ready input, similar to Assist 3 Ready Input (29.160).
5 Assist 3 running input, similar to Assist 3 Running Input (29.161).
6 Assist 4 ready input, similar to Assist 4 Ready Input (29.166).
7 Assist 4 running input, similar to Assist 4 Running Input (29.167).


Parameter29.153  Pump Status Word 1
Short descriptionPump software status word 1
ModeRFC‑A
Minimum0
(Display: 0000000000000000)
Maximum65535
(Display: 1111111111111111)
Default0
(Display: 0000000000000000)
Units 
Type16 Bit VolatileUpdate RateBackground
Display FormatBinaryDecimal Places0
CodingRW, NC, BU

This is remote status word 1, intended to be used by a HMI or PLC to control the Pump drive when Control Input Mode (29.012) = Ctrl Wrd or Ctrl Wrd & Input.
The following status bits are available:

Bit Functionality
0 Auto selected output, similar to Auto Selected Output (29.018).
1 Hand selected output, similar to Hand Selected Output (29.019).
2 Auto operational output, similar to Auto Operational Output (29.021).
3 Auto running output, similar to Auto Running Output (29.020).
4 PID software enable, similar to PID Software Enable (29.038).
5 PID at setpoint output, similar to PID At Setpoint Output (29.046).
6 PID feedback low output, similar to PID Feedback Low Output (29.047).
7 Sleep required output, similar to Sleep Required Output (29.053).
8 Sleep active output, similar to Sleep Active Output (29.054).
9 Pipe fill done output, similar to Pipe Fill Done Output (29.078).
10 Cleaning active output, similar to Clean Active Output (29.104).
11 Cleaning was triggered due to load current threshold as configured by Clean On Load Current Low Threshold (29.099) or Clean On Load Current High Threshold (29.098).
12 Cleaning was triggered due to motor load accumulator build up as indicated by Motor Overload Alarm (10.017).
13 Cleaning was triggered due to the Clean On Interval Time (29.096) elapsing.
14 Cleaning was triggered on start up. See Clean On Start (29.089).
15 Cleaning was triggered due to manual input. See Clean Manual Input (29.088).


Parameter29.154  Pump Status Word 2
Short descriptionPump software status word 2
ModeRFC‑A
Minimum0
(Display: 0000000000000000)
Maximum65535
(Display: 1111111111111111)
Default0
(Display: 0000000000000000)
Units 
Type16 Bit VolatileUpdate RateBackground
Display FormatBinaryDecimal Places0
CodingRW, NC, BU

This is remote status word 2, intended to be used by a HMI or PLC to control the Pump drive when Control Input Mode (29.012) = Ctrl Wrd or Ctrl Wrd & Input.
The following status bits are available:

Bit Functionality
0 Assist 1 run output, similar to Assist 1 Run Output (29.107).
1 Assist 2 run output, similar to Assist 2 Run Output (29.113).
2 Assist 3 run output, similar to Assist 3 Run Output (29.159).
3 Assist 4 run output, similar to Assist 4 Run Output (29.165).
4 Not Stop Input, similar to Not Stop Input (29.190). Only used in Basic mode, where Pump Control Mode (29.011) = Basic.
5 Start Input, similar to Start Input (29.191). Only used in Basic mode, where Pump Control Mode (29.011) = Basic.


Parameter29.155  Pump Alarm Word
Short descriptionPump software alarm word
ModeRFC‑A
Minimum0
(Display: 0000000000000000)
Maximum65535
(Display: 1111111111111111)
Default0
(Display: 0000000000000000)
Units 
Type16 Bit VolatileUpdate RateBackground
Display FormatBinaryDecimal Places0
CodingRW, NC, BU

This is the remote alarm word, intended to be used by a HMI or PLC to control the Pump drive when Control Input Mode (29.012) = Ctrl Wrd or Ctrl Wrd & Input.
The following alarm bits are available:

Bit Functionality
0 No flow switch output, similar to No Flow Switch Output (29.068).
1 No flow by software detection output, similar to No Flow Output (29.074).
2 Low flow stop output, similar to Low Flow Meter Stop Output (29.065).
3 At max drive reference output, similar to At Maximum Drive Reference  (29.084).
4 PID feedback high alarm output, similar to PID Feedback High Alarm Output (29.040).
5 Clean per hour alarm output, similar to Clean Per Hour Alarm Output (29.105).
6 Over-cycle limit alarm output, similar to Over-cycle Alarm Output (29.131).
7 Dry well low load alarm output, similar to Dry Well Low Load Alarm Output (29.062).
8 Reserved
9 Assist 1 start lockout output, similar to Assist 1 Lockout Output (29.112).
10 Assist 2 start lockout output, similar to Assist 2 Lockout Output (29.118).
11 Assist 3 start lockout output, similar to Assist 3 Lockout Output (29.164).
12 Assist 4 start lockout output, similar to Assist 4 Lockout Output (29.170).


Parameter29.156  Pump Software Stop
Short descriptionThis runs or stops the pump software
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type8 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, TE, BU

ValueText
0Run Software
1Stop Software

When set to Run Software, the pump software runs. When set to Stop Software, the pump software stops, where all associated functionality ceases. This is intended to be used as a diagnostic aid by Nidec Control Techniques personnel or to permit access to Control Word (06.042) It is recomended to leave it set to the default of Run Software.

Control Word Enable (06.043) and Control Word (06.042) may only be used when the pump software has been disabled by setting Pump Software Stop (29.156) to Stop Software. This allows support for motion profiles such as DS402, where the pump control is implemented on a 3rd party controller.

Control Word Enable (06.043) is continually written to Off(0) while the pump software is running i.e. when Pump Software Stop (29.156) = Stop Software.


Parameter29.157  Motor Type
Short descriptionUse this to select the system motor type. Reset drive to accept a new selection.
ModeRFC‑A
Minimum0Maximum1
Default1Units 
Type8 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, TE, BU

ValueText
0Induction
1Permanent-magnet

This parameter simplifies setup and selection of the application motor. To action the motor selection a drive reset must be actioned e.g. by pressing the red reset button on the keypad.

The following options are available:

Motor type Value Description
Induction 0 When Motor Type (29.157) changes to Induction and a reset is performed, the drive will change to open-loop mode for induction motors and the previous regional defaults will be applied.
Permanent-magnet 1 When Motor Type (29.157) changes to Permanent-magnet and a reset is performed, the drive will change to RFC-S mode for servo motors and the previous regional defaults will be applied. By default the motor will be operating in sensorless mode i.e. no speed feedback device is required to run the motor.

 


Parameter29.158  Keypad Power Up In Auto
Short descriptionWhen set to 1 and in Keypad mode, on power up run in Auto
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type1 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW

This feature allows the user to decide how the F600 should behave on power up when controlled by the keypad. To use this feature, Control Input Mode (29.012) must be set to Input & Keypad and the drive must only be controlled by the keypad.

When set to 0, on power up provided the STO input has been set to 24V the system will power up in the Off (Ready) state, where the pump will be stopped.

When set to 1, on power up provided the STO input has been set to 24V, the system will power up and automatically select Auto, allowing continued pump operation after a transient loss of supply voltage.


Parameter29.159  Assist 3 Run Output
Short descriptionOff = Stop, On = Run.
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type8 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, PR, TE, NC, BU

ValueText
0Off
1On

This is the Run command output for Assist 3. A digital output must be routed to this parameter where the subsequent 24V signal is connected to the run Input of Soft Starter Assist 3.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.160  Assist 3 Ready Input
Short descriptionOff = Not ready, On = Ready.
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type8 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, TE, NC, BU

ValueText
0Off
1On

Assist 3 Ready Input (29.160) is only used when Assist Control Mode (29.106) = Full I/O.

This is the Ready feedback input for Assist 3. A digital input must be routed to this parameter where a 24V signal is connected to a ready or healthy output from Soft Starter Assist 3.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.161  Assist 3 Running Input
Short descriptionOff = Not Running, On = Running.
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type8 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, TE, NC, BU

ValueText
0Off
1On

Assist 3 Running Input (29.161) is only used when Assist Control Mode (29.106) = Full I/O.

This is the Running feedback input for Assist 3. A digital input must be routed to this parameter where a 24V signal is connected to a running output from Soft Starter Assist 3.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.162  Assist 3 Runtime
Short descriptionAssist 3 run time since power up in minutes
ModeRFC‑A
Minimum0Maximum2147483647
Default0Unitsminutes
Type32 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, PR, NC

This indicates the running time for Assist Soft Starter 3 in minutes since the Leader drive was powered up.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.163  Assist 3 Lockout Countdown
Short descriptionIndicates the time remaining until assist 3 can be restarted
ModeRFC‑A
Minimum0.0Maximum3600.0
Default0.0Unitss
Type16 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places1
CodingRW, PR, NC, BU

In the event that Assist Starts Per Hour (29.120) has been reached by Assist Soft Starter 3, Assist 3 Lockout Countdown (29.163) indicates the remaining time in seconds that this Soft Starter is locked out for to allow time for it to cool down.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.164  Assist 3 Lockout Output
Short descriptionIndicates when Assist 3 has been locked out due to too many starts per hour
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type8 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, PR, TE, NC, BU

ValueText
0Off
1On

In the event that Assist Starts Per Hour (29.120) has been reached by Assist Soft Starter 1, Assist 3 Lockout Output (29.164) indicates when this Soft Starter is locked out to allow time for it to cool down.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.165  Assist 4 Run Output
Short descriptionOff = Stop, On = Run.
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type8 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, PR, TE, NC, BU

ValueText
0Off
1On

This is the Run command output for Assist 4. A digital output must be routed to this parameter where the subsequent 24V signal is connected to the run Input of Soft Starter Assist 4.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.166  Assist 4 Ready Input
Short descriptionOff = Not ready, On = Ready.
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type8 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, TE, NC

ValueText
0Off
1On

Assist 4 Ready Input (29.166) is only used when Assist Control Mode (29.106) = Full I/O.

This is the Ready feedback input for Assist 4. A digital input must be routed to this parameter where a 24V signal is connected to a ready or healthy output from Soft Starter Assist 4.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.167  Assist 4 Running Input
Short descriptionOff = Not Running, On = Running.
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type8 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, TE, NC

ValueText
0Off
1On

Assist 4 Running Input (29.167) is only used when Assist Control Mode (29.106) = Full I/O.

This is the Running feedback input for Assist 4. A digital input must be routed to this parameter where a 24V signal is connected to a running output from Soft Starter Assist 4.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.168  Assist 4 Runtime
Short descriptionAssist 4 run time since power up in minutes
ModeRFC‑A
Minimum0Maximum2147483647
Default0Unitsminutes
Type32 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, PR, NC

This indicates the running time for Assist Soft Starter 4 in minutes since the Leader drive was powered up.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.169  Assist 4 Lockout Countdown
Short descriptionIndicates the time remaining until assist 4 can be restarted
ModeRFC‑A
Minimum0.0Maximum3600.0
Default0.0Unitss
Type16 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places1
CodingRW, PR, NC, BU

In the event that Assist Starts Per Hour (29.120) has been reached by Assist Soft Starter 4, Assist 3 Lockout Countdown (29.163) indicates the remaining time in seconds that this Soft Starter is locked out for to allow time for it to cool down.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.170  Assist 4 Lockout Output
Short descriptionIndicates when Assist 4 has been locked out due to too many starts per hour
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type8 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, PR, TE, NC, BU

ValueText
0Off
1On

In the event that Assist Starts Per Hour (29.120) has been reached by Assist Soft Starter 4, Assist 4 Lockout Output (29.170) indicates when this Soft Starter is locked out to allow time for it to cool down.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.171  Number Of Pumps
Short descriptionSets the number of pumps in the system used in Cascade and Multi-leader
ModeRFC‑A
Minimum0Maximum5
Default0Units 
Type8 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, BU

This defines the total number of pumps in the system, when Pump Control Mode (29.011) = Cascade or Multi-leader. When Pump Control Mode (29.011) = Single Pump, it is assumed that there is 1 pump operating where the setting of this parameter has no effect. Changes to Number Of Pumps (29.171) are only accepted when the drive is not active, i.e. Drive Active (10.002) = Off(0).

When set to 0, it is assumed that the maximum number of pumps are available to run. When Pump Control Mode (29.011) = Cascade the maximum is 5 pumps (1 Leader drive and 4 soft starter assists). When Pump Control Mode (29.011) = Multi-leader, the maximum is 3 pumps (1 Leader drive and 2 assist drives).

When set >0 this defines the specific number of pumps in the system. Note that When Pump Control Mode (29.011) = Multi-leader, values >3 are internally limited to 3.

When Pump Control Mode (29.011) = Cascade, Number Of Pumps (29.171) affects which assists will be considered as part of the system:

When Pump Control Mode (29.011) = Multi-leader, Number Of Pumps (29.171) affects which assists will be considered as part of the system:

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.

When Pump Control Mode (29.011) = Cascade Leader, Number Of Pumps (29.171) affects which assists will be considered as part of the system:


Parameter29.172  Flow Compensation Enable
Short descriptionWhen set to 1, flow compensation is enabled.
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type1 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW

When set to Off(0), Flow Compensation is disabled and Flow Compensation Output Limit (29.178) has no effect on PID Selected Setpoint (29.028) ..
When set to On(1), Flow Compensation is enabled, and Flow Compensation Output Limit (29.178) modifies PID Selected Setpoint (29.028) with changes in output speed or frequency to simulate the effect of a pressure sensor fitted at the end of a water distribution network, where the sensor has been fitted close to the pump instead. In this situation Flow Compensation offers a significant energy saving at reduced flow.

The ideal setup for a constant pressure pumping system is to have the pressure transducer located near the end of the water distribution pipeline. For practical reasons this is not always possible, and in this situation the pressure transducer is fitted close to the pump discharge outlet, where without flow compensation, there can be significant energy losses at reduced flow i.e. flow less than the system design value.

In the previous image the feedback is fitted close to the pump instead of at the end of the water distribution network some distance away, as indicated by the second sensor with dotted connection.

Energy is saved when Flow Compensation is enabled by reducing the pressure setpoint in proportion to the motor frequency or speed. The following diagram illustrates where energy can be saved when using Flow Compensation.

The flow compensation curve start and end points are configured using Flow Compensation No Flow Speed (29.173) to Flow Compensation Curve Percentage (29.177), as illustrated in the following diagram:

Flow Compensation No Flow Speed (29.173) and Flow Compensation No Flow Setpoint (29.174) define the starting point for the flow compensation curve. Flow Compensation Working Speed (29.175) and Flow Compensation Working Speed (29.175) define the end point for the flow compensation curve.

Where the motor frequency or speed is in between start and end point, an interpolation calculation is used to define the maximum setpoint, where shape of interpolated pressure profile is set using Flow Compensation Curve Percentage (29.177). When Flow Compensation Curve Percentage (29.177) = 0% linear interpolation is used, when Flow Compensation Curve Percentage (29.177) = 100% square interpolation is used, values in the range 1% to 99% adopt a hybrid curve blended between linear and square.

The data for the pump curve may be derived from the system design or made using an estimation using the pump data sheet.

The output from the interpolator, as indicated by Flow Compensation Output Limit (29.178), limits the value seen in PID Selected Setpoint (29.028). When Flow Compensation Enable (29.172) = 0, Flow Compensation Curve Percentage (29.177) does not apply.

For Cascade and Multi-leader systems Number Of Pumps (29.171) must be set so that the PID setpoint limit interpolation calculation operates in the correct region of the curve for a given number of running pumps. E.g. for a Cascade system operating with 1 drive and 2 assist soft starters, Number Of Pumps (29.171) = 3. Note that in a multi-pump system, the No Flow end of the curve is used when only the leader is operating, but the running end of the curve is when all of the pumps are running at the design flow and pressure.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect. 
 


Parameter29.173  Flow Compensation No Flow Speed
Short descriptionSets the speed for the no flow end of the flow compensation curve
ModeRFC‑A
Minimum0.0Maximum3000.0
Default750.0Units 
Type32 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places1
CodingRW

Flow Compensation No Flow Speed (29.173) defines the flow compensation feature no flow frequency or speed. This is found by running the system in hand mode, with any balancing valves shut, and the furthest valve on the water distribution network open. Increase the hand mode reference in small steps until flow begins at the furthest valve or tap, then set Flow Compensation No Flow Speed (29.173) to the hand mode reference value as seen Post Ramp Reference (02.001).

In a Multi-leader system, this value must also be set in the other drives Flow Compensation No Flow Speed (29.173) parameter.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.174  Flow Compensation No Flow Setpoint
Short descriptionSets the setpoint for the no flow end of the flow compensation curve
ModeRFC‑A
Minimum0.00Maximum327.67
Default50.00Units 
Type16 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places2
CodingRW

Flow Compensation No Flow Setpoint (29.174) defines the flow compensation feature no flow setpoint. This is found by running the system in hand mode, with any balancing valves shut, and the furthest valve on the water distribution network open. Increase the hand mode reference in small steps until flow begins at the furthest valve, then set Flow Compensation No Flow Setpoint (29.174) to the value seen in PID Final Feedback (29.036).

In a Multi-leader system, this value must be also set in the other drives Flow Compensation No Flow Setpoint (29.174) parameter.

The units of this parameter, are defined by the feedback type and scaling, PID Feedback Minimum Scaling (29.031) and PID Feedback Maximum Scaling (29.032), e.g. if the feedback transducer connected to Analog input 1 is a pressure sensor then this is a pressure setpoint with the same scaling. The units shown on the keypad display and the the number of decimal places for this parameter may be selected using PID Unit Select (29.184) and PID Unit Decimal Places (29.185).

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.175  Flow Compensation Working Speed
Short descriptionSets the speed for the working end of the flow compensation curve
ModeRFC‑A
Minimum0.0Maximum3000.0
Default1500.0Units 
Type32 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places1
CodingRW

Flow Compensation Working Speed (29.175) defines the frequency or speed at which the design pressure and flow are met when all pumps in the system are working at full capacity. This may be found from the system design or by reading the pump data sheet, whichever is available.

In a Multi-leader system, this value must also be set in the other drives Flow Compensation Working Speed (29.175) parameter.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.176  Flow Compensation Working Setpoint
Short descriptionSets the setpoint for the working end of the flow compensation curve
ModeRFC‑A
Minimum0.00Maximum327.67
Default100.00Units 
Type16 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places2
CodingRW

Flow Compensation Working Setpoint (29.176) defines the setpoint where the system design pressure and flow are met when all pumps in the system are working at full capacity. This may be found from the system design or by reading the pump data sheet, whichever is available.

In a Multi-leader system, this value must also be set in the other drives Flow Compensation Working Setpoint (29.176) parameter.

The units of this parameter, are defined by the feedback type and scaling, PID Feedback Minimum Scaling (29.031) and PID Feedback Maximum Scaling (29.032), e.g. if the feedback transducer connected to Analog input 1 is a pressure sensor then this is a pressure setpoint with the same scaling. The units shown on the keypad display and the the number of decimal places for this parameter may be selected using PID Unit Select (29.184) and PID Unit Decimal Places (29.185).

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.177  Flow Compensation Curve Percentage
Short description0% = Linear interpolation, 100% square interpolation
ModeRFC‑A
Minimum0.00Maximum100.00
Default100.00Units%
Type16 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places2
CodingRW

Flow Compensation Curve Percentage (29.177) defines the setpoint limit curve used during flow compensation. Where the motor frequency or speed is in between start and end point, an interpolation calculation is used to define the maximum setpoint, where shape of interpolation and shape of the pressure profile is set using Flow Compensation Curve Percentage (29.177). When Flow Compensation Curve Percentage (29.177) = 0% linear interpolation is used, when Flow Compensation Curve Percentage (29.177) = 100% square interpolation is used, values in the range 1% to 99% adopt a hybrid curve blended between linear and square interpolation.

In a Multi-leader system, this value must also be set in the other drives Flow Compensation Curve Percentage (29.177) parameter.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.178  Flow Compensation Output Limit
Short descriptionIndicates the output limit applied to Pr29.028
ModeRFC‑A
Minimum0.00Maximum327.67
Default0.00Units 
Type16 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places2
CodingRW

Flow Compensation Output Limit (29.178) indicates the limit applied to PID Selected Setpoint (29.028) for flow compensation, at a given motor speed or frequency and number of running assists.

The units of this parameter, are defined by the feedback type and scaling, PID Feedback Minimum Scaling (29.031) and PID Feedback Maximum Scaling (29.032), e.g. if the feedback transducer connected to Analog input 1 is a pressure sensor then this is a pressure limit with the same scaling. The units shown on the keypad display and the the number of decimal places for this parameter may be selected using PID Unit Select (29.184) and PID Unit Decimal Places (29.185).

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.179  Flow Meter Source Select
Short descriptionSelects either pulsed or analog flow meter feedback
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type8 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, TE, BU

ValueTextDescription
0PulsePulsed output flow meter
1AnalogAnalog output flow meter

When Flow Meter Source Select (29.179) is set to Pulse, pulsed flow meter is selected where the pulsed flow transducer is connected to a digital input routed to Flow Meter Pulse Input (29.008), where the pulses are counted, and the flow is derived using the Flow Scaling (29.007). The result is displayed in Flow (29.005).

When Flow Meter Source Select (29.179) is set to Analog, a 4-20mA or 0 to 10V flow transducer is connected to an analog input routed to Flow Meter Analog Input (29.180), where the feedback is displayed as a percentage. Flow Meter Analog Minimum Scaling (29.181) and Flow Meter Analog Maximum Scaling (29.182) are used to scale value seen in Flow Meter Analog Input (29.180) from percentage to flow units. The result is displayed in Flow (29.005). In this mode Flow Scaling (29.007) and Volume Scaling (29.006) should be set to 1.000000 unless additional scaling is required.


In both modes Flow (29.005) is calculated.


 


Parameter29.180  Flow Meter Analog Input
Short descriptionA destination for an analog input with a flow meter connected
ModeRFC‑A
Minimum-100.00Maximum100.00
Default0.00Units%
Type16 Bit VolatileUpdate Rate4ms
Display FormatStandardDecimal Places2
CodingRW

Indicates the analog flow sensor measurement as a percentage. A drive analog input with a flow transducer connected must be routed to this parameter. Flow Meter Analog Minimum Scaling (29.181) and Flow Meter Analog Maximum Scaling (29.182) are used to scale value seen in Flow Meter Analog Input (29.180) from percentage to flow units, e.g. litres per minute. The result is displayed in Flow (29.005).

When Flow Meter Source Select (29.179) is set to Analog, Flow Scaling (29.007) and Volume Scaling (29.006) should be set to 1.000000 unless additional scaling is required.

This parameter is only used when Flow Meter Source Select (29.179) is set to Analog.


Parameter29.181  Flow Meter Analog Minimum Scaling
Short descriptionDefines the minimum value represented by the lowest amplitude analog signal input
ModeRFC‑A
Minimum0.0Maximum3276.7
Default0.0Units 
Type16 Bit User SaveUpdate Rate4ms
Display FormatStandardDecimal Places1
CodingRW

Flow Meter Analog Minimum Scaling (29.181) defines the minimum scaling value when an analog flow sensor is used. Flow Meter Analog Minimum Scaling (29.181) and Flow Meter Analog Maximum Scaling (29.182) are used to scale value seen in Flow Meter Analog Input (29.180) from percentage to flow units, e.g. litres per minute. The result is displayed in Flow (29.005).

This parameter is only used when Flow Meter Source Select (29.179) is set to Analog.


Parameter29.182  Flow Meter Analog Maximum Scaling
Short descriptionDefines the minimum value represented by the highest amplitude analog signal input
ModeRFC‑A
Minimum0.1Maximum3276.7
Default100.0Units 
Type16 Bit User SaveUpdate Rate4ms
Display FormatStandardDecimal Places1
CodingRW

Flow Meter Analog Maximum Scaling (29.182) defines the maximum scaling value when an analog flow sensor is used. Flow Meter Analog Minimum Scaling (29.181) and Flow Meter Analog Maximum Scaling (29.182) are used to scale value seen in Flow Meter Analog Input (29.180) from percentage to flow units, e.g. litres per minute. The result is displayed in Flow (29.005).

This parameter is only used when Flow Meter Source Select (29.179) is set to Analog.


Parameter29.183  Flow Meter Analog Time Base
Short descriptionDefines the time base of the flow meter units in seconds, minutes or hours
ModeRFC‑A
Minimum0Maximum2
Default1Units 
Type8 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, TE, BU

ValueTextDescription
0Per secondThe flow meter units are volume/second
1Per minuteThe flow meter units are volume/minute
2Per hourThe flow meter units are volume/hour

This defines the time base of the analog flow sensor, e.g. if the sensor is in litres per minute then this parameter is set to “Per minute”. The correct setting of this parameter is essential for the correct calculation of the volume data when Flow Meter Source Select (29.179) is set to Analog.


Parameter29.184  PID Unit Select
Short descriptionDefines the unit type shown on the keypad for all main process PID related parameters
ModeRFC‑A
Minimum0Maximum158
Default71Units 
Type8 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, TE, BU

PID Unit Select (29.184) defines the units shown on the keypad by all parameters related to the main process PID control in Menu 29. The units of parameters PID Setpoint 0 (29.022), PID Setpoint 1 (29.023), PID Setpoint 2 (29.024), PID Setpoint 3 (29.025), PID Selected Setpoint (29.028), PID Final Setpoint (29.029), PID Feedback Minimum Scaling (29.031), PID Feedback Minimum Scaling (29.031), PID Feedback Maximum Scaling (29.032), PID Final Feedback (29.036), PID Error (29.037), PID Feedback High Alarm Threshold (29.039), PID Feedback High Trip Threshold (29.041), PID Feedback Low Threshold (29.044), PID At Setpoint Band (29.045), Wake Detect Feedback Threshold (29.049), No Flow Setpoint Reduction (29.073) , Pipe Fill Threshold (29.076), Flow Compensation No Flow Setpoint (29.174) , Flow Compensation Working Setpoint (29.176), and Flow Compensation Output Limit (29.178) are affected by the setting of this parameter.

This feature requires keypad firmware >=V02.00.03.02, keypad language file >=V04.04.05.38, Pump Drive F600 Software V01.00.02.00, and drive firmware drive firmware >=V04.24.01.00 to operate correctly.

When selected, the following unit types produce a blank unit on the keypad display:
No unit, CU, GPU, GSU, CLSU, GAU, CLAU, GJU, CLJU, GPIDU.


Parameter29.185  PID Unit Decimal Places
Short descriptionDefines the number of decimal places shown on the keypad display for all main process PID related units
ModeRFC‑A
Minimum0Maximum5
Default2Units 
Type16 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW

PID Unit Decimal Places (29.185) allows the decimal places shown on the keypad display for PID related units to be adjusted allowing for PID feedback sensors with a large integer range to be accommodated. Setting a value of 2, (the default), gives 2 decimal places on the display, setting a value of 1, (the default), gives 1 decimal place on the display etc.
E.g. a sensor has a range of 0 to 350 psi, but the default range of Pr29.032 is 0.01 to 327.67, by setting 29.185 to 1, the range becomes 0.1 to 3276.7 where 350 may be accommodated.

 The decimal places of parameters PID Setpoint 0 (29.022), PID Setpoint 1 (29.023), PID Setpoint 2 (29.024), PID Setpoint 3 (29.025), PID Selected Setpoint (29.028), PID Final Setpoint (29.029), PID Feedback Minimum Scaling (29.031), PID Feedback Minimum Scaling (29.031), PID Feedback Maximum Scaling (29.032), PID Final Feedback (29.036), PID Error (29.037), PID Feedback High Alarm Threshold (29.039), PID Feedback High Trip Threshold (29.041), PID Feedback Low Threshold (29.044), PID At Setpoint Band (29.045), Wake Detect Feedback Threshold (29.049), No Flow Setpoint Reduction (29.073) , Pipe Fill Threshold (29.076), Flow Compensation No Flow Setpoint (29.174) , Flow Compensation Working Setpoint (29.176), and Flow Compensation Output Limit (29.178) are affected by the setting of this parameter.

This feature requires keypad firmware >=V02.00.03.02, keypad language file >=V04.04.05.38, Pump Drive F600 Software V01.00.02.00, and drive firmware drive firmware >=V04.24.01.00 to operate correctly.

 


Parameter29.186  External Wake Input
Short descriptionAllows an external controller to control when to wake the drive
ModeRFC‑A
Minimum0Maximum1
Default1Units 
Type1 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, BU

External Wake Input (29.186) allows a plug-in option such as an MCi200 or MCi210 to affect when the F600 wakes by logical ANDing this bit with the result of the F600 wake logic, (as controlled by Wake Detect Feedback Threshold (29.049) and Wake Detect Delay (29.050)).

When set to 1 and provided the drive is sleeping, this indicates that the external wake control is satisfied that the system must wake, and provided the F600 wake logic is satisfied, the drive will wake. When set to 0 and provided the drive is sleeping, this indicates that the External wake control isn’t satisfied where the system must remain in the sleeping state and will do so regardless of the state of the F600 wake logic.


Wake Detect Delay (29.050) has no effect on when the external wake is actioned i.e. the wake bit is applied directly with no delay. It is expected that the user will program the external wake delay into their software. Where external wake control isn’t required set this parameter to 1. This parameter has no effect if the drive is already running.

When the Pump Drive F600 us used as an assist in a Multi-leader system, the system lead drive control supersedes this input where it may be commanded to run. It is intended that in a multi-leader system External Wake Input (29.186) is activated on the system leader, where the assist drives will simply shut down using the standard assist control mechanism.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.187  External Sleep Input
Short descriptionAllows an external controller to request the drive sleep
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type1 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW

External Sleep Input (29.187) allows a plug-in option such as an MCi200 or MCi210 to affect when the F600 sleeps by logical ORing this bit with the result of the F600 sleep logic, (as controlled by Sleep Detect Speed Threshold (29.051) and Sleep Detect Delay (29.052)).


When set to 1 and provided the drive is in a running state, this indicates that the External Sleep control is satisfied that the system must go to sleep. This control acts in parallel with the F600 sleep system, where either can cause the system to sleep. It is recommended that once the system is in the sleeping state as indicated by Operating Status (29.003), the external sleep bit must be set back to 0.

When set to 0, this indicates F600 External sleep control doesn’t require a sleep, where the system sleep control is handled by F600 sleep logic.
In a Cascade or Multi-leader system, when an external sleep request has been made, all assist drives / soft starters will be shut down prior the leader drive shutting down, regardless of the demand from the main process PID.


Sleep Detect Delay (29.052) has no effect on when the external sleep is actioned, i.e. the sleep bit is applied directly with no delay. It is expected that the user will program the external sleep delay into their software. Where external sleep control isn’t required set this parameter to 0. This parameter has no effect if the drive is already sleeping.

When the Pump Drive F600 us used as an assist in a Multi-leader system, the system lead drive control supersedes this input where it may be commanded to run. It is intended that in a multi-leader system External Sleep Input (29.187) is activated on the system leader, where the assist drives will simply shut down using the standard assist control mechanism.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


 


Parameter29.188  PID Feedback High Sleep Enable
Short descriptionWhen set to On(1) in the event of a PID Feedback High Alarm the system will sleep to prevent further increase.
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type1 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW

When set to Off(0), and PID Final Feedback (29.036) is > PID Feedback High Alarm Threshold (29.039), PID Feedback High Alarm Output (29.040) is set to On(1) with no further action.


When set to On(1), and PID Final Feedback (29.036) is > PID Feedback High Alarm Threshold (29.039), PID Feedback High Alarm Output (29.040) is set to On(1) and the drive with any assists the may be running will be rapidly shutdown, where the system will go to sleep. In this way further increase of the PID Feedback is prevented. When this happens Sleep Detect Delay (29.052) and Remove Assist Delay (29.124) are ignored.

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.189  Assist Sleep Detect Speed Threshold
Short descriptionWhen set > 0 this defines the assist sleep threshold. When set to 0, the normal sleep detect threshold is used by assists.
ModeRFC‑A
Minimum0.0Maximum3000.0
Default0.0Units 
Type32 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places1
CodingRW

When set to 0, the lead drive and any assist drives or soft starters will be shut down using Sleep Detect Speed Threshold (29.051). 

When set to 1, assist drives or soft starters will be shut down using Assist Sleep Detect Speed Threshold (29.189). The lead pump drive continues to use Sleep Detect Speed Threshold (29.051). The separate assist sleep threshold is helpful in situations where:
•  The assists need to be shut down at a higher assist sleep frequency in order to save energy.
•  The assists must be shut down when operating at the pumps maximum pressure with a closed output valve where a higher assist sleep frequency can avoid assists remaining on. 

Note that Assist Sleep Detect Speed Threshold (29.189) must be set >=  Positive Minimum Reference Clamp (01.004), so that the  assists will sleep in Auto mode. 

When basic mode is selected, (Pump Control Mode (29.011) = Basic), this feature is disabled internally where all user parameters related to this feature will cease to have an effect.


Parameter29.190  Not Stop Input
Short descriptionWhen set to 1, permit the drive to run in hand mode. When set to 0, unlatch an active hand run command
ModeRFC‑A
Minimum0Maximum1
Default1Units 
Type1 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, BU

Not Stop Input (29.190) is only used when Pump Control Mode (29.011) = Basic, in all other modes it has no effect.

In Basic mode, to permit the drive to run when Hand is selected, a digital input with 24V applied must be routed to Not Stop Input (29.190), where this input is set to On(1).

If  Hand mode is selected via Hand Select Input (29.013) or the Pump Control Word 1 (29.151), if Not Stop Input (29.190) = Off(0) any active run in hand mode will stop, or if Not Stop Input (29.190) = On(1) hand will be permitted to run. If Auto mode is selected Not Stop Input (29.190) is ignored. Note that to run the motor Start Input (29.191) must be set to 1.

The following diagram shows two examples of how the control connections can be made in Basic mode (Pump Control Mode (29.011) = Basic) where the Not Stop and Start inputs are active:


Parameter29.191  Start Input
Short descriptionWhen set to 1, command the drive to run. When set to 0, no action.
ModeRFC‑A
Minimum0Maximum1
Default1Units 
Type1 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, BU

Start Input (29.191) is only used when Pump Control Mode (29.011) = Basic, in all other modes it has no effect.

In Basic mode, to run the drive in Hand or Auto a digital input with 24V applied must be routed to Start Input (29.191).

If Hand or Auto mode is selected via Hand Select Input (29.013), Auto Select Input (29.015) or the Pump Control Word 1 (29.151), and Not Stop Input (29.190) = On(1), when Start Input (29.191) is set to On(1), the drive will run the motor.

In Hand mode, this input is latching so that a momentary switch may be used to run the motor. In Hand mode the motor may be run or stopped using push button momentary start and stop switches for local control.

In Auto mode this input is non-latching and must be set constantly to On(1) via a digital input when the motor is required to run. In Auto mode the motor may be run or stopped using ordinary switches for remote control where selecting Auto must activate both the Auto Select Input (29.015) and the Start Input (29.191).

The following diagram shows two examples of how the control connections can be made in Basic mode (Pump Control Mode (29.011) = Basic) where the Not Stop and Start inputs are active:
 


Parameter29.192  PID Error Threshold Add Assist
Short descriptionSets a minimum PID error threshold for adding assist pumps to the system
ModeRFC‑A
Minimum0.00Maximum327.67
Default0.00Units 
Type16 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places2
CodingRW

When PID Error Threshold Add Assist (29.192) is > 0.00 a new condition for adding assist pumps to the system is included. When PID Error Threshold Add Assist (29.192) = 0.00, this parameter has no function.
When adding an assist pump, PID Error (29.037) must be higher than PID Error Threshold Add Assist (29.192) to start the Add Assist Delay (29.122). This prevents a situation where the pressure feedback is below the PID setpoint, the output frequency is high enough to add a new assisted pump, but the pressure error is very small, so adding a new pump is not efficient or could end in too much pressure in the in the pump distribution pipes.


Parameter29.193  PID Error Threshold Remove Assist Pumps
Short descriptionPID Error Threshold for removing assist pumps
ModeRFC‑A
Minimum-327.68Maximum327.67
Default0.00Units 
Type32 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places2
CodingRW

When Pump Control Mode (29.011) = Cascade or Cascade Leader, this defines the PID error threshold used when removing an assist. When this parameter is greater than 0, it defines the minimum percentage of PID error required before a cascade assist is removed. 

When this parameter is set to 0, assists will be removed when Sleep Detect Speed Threshold (29.051) or Assist Sleep Detect Speed Threshold (29.189) is reached and Remove Assist Delay (29.124) elapses.


Parameter29.194  Cascade Leader Alternation Mode
Short descriptionDefines the conditions required for the cascade Leader to alternate.
ModeRFC‑A
Minimum0Maximum2
Default0Units 
Type8 Bit User SaveUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, TE, BU

ValueTextDescription
0SleepingThe alternation happens when the system goes to sleep state under auto mode conditions
1Auto Not SelectThe alternation happens when the system the auto signal is removed
2BothThe alternation happes when sleeeping or when the auto signal is removed

Defines the logic used to alternate the cascader leader when Pump Control Mode (29.011) = Cascade Leader.

The following table show the options available:

Mode Value Description
Sleeping 0 When this mode is selected the Cascade Leader alternates when the system is sleeping.
Auto Not Select 1 When this mode is selected the Cascade Leader alternates when the Auto command is inactive.
Both 2 When this mode is selected the Cascade Leader alternates when the system is sleeping and when the Auto command is inactive.